Siemens 440 manual P21723 Threshold DC-link voltage, P21733 Delay time DC-link voltage, 216

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 216
Image 216

Parameter Description

Issue 01/06

P2172[3] Threshold DC-link voltage

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: V

Def:

800

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

2000

Defines DC link voltage to be compared to actual voltage as illustrated in the diagram below.

Level

3

Vdc

P2172

Vdc_act < P2172

r0053 1 Bit07

0

 

Vdc_act > P2172

P2173

 

r0053 1 Bit08

0

P2173

Index:

t

t

t

P2172[0] : 1st. Drive data set (DDS)

P2172[1] : 2nd. Drive data set (DDS)

P2172[2] : 3rd. Drive data set (DDS)

Note:

This voltage controls bits 7 and 8 in status word 3 (r0053).

P2173[3] Delay time DC-link voltage

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: ms

Def:

10

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

10000

Defines delay time prior to activation of threshold comparison.

Index:

P2173[0] : 1st. Drive data set (DDS)

P2173[1] : 2nd. Drive data set (DDS)

P2173[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2172 (threshold DC-link voltage)