Issue 01/06

Parameter Description

P2162[3]

Hysteresis freq. for overfreq.

 

Min:

0.00

 

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

20.00

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

650.00

Hysteresis frequency for overfrequency-detection as illustrated in the diagram below.

f_act > f_max

Max. frequency

 

0.00 ... 650.00 [Hz]

 

P1082.D (50.00)

Level

2

f_act

 

1

{

0

 

f_act > f_max

r2197 Bit06

Overspd. hyst.freq

0.00 ... 650.00 [Hz] P2162.D (20.00)

Index:

 

P2162[0]

: 1st. Drive data set (DDS)

P2162[1]

: 2nd. Drive data set (DDS)

P2162[2]

: 3rd. Drive data set (DDS)

P2163[3] Entry freq. for perm. deviation

 

Min:

0.00

Level

 

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

3.00

2

 

 

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

20.00

 

Threshold for detecting frequency deviation from setpoint as illustrated in the diagram P2164.

Index:

 

P2163[0]

: 1st. Drive data set (DDS)

P2163[1]

: 2nd. Drive data set (DDS)

P2163[2]

: 3rd. Drive data set (DDS)

P2164[3] Hysteresis frequency deviation

 

Min:

0.00

Level

 

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

3.00

3

 

 

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

10.00

 

Hysteresis frequency for detecting permitted deviation (from setpoint). This frequency controls bit 8 in status word 1 (r0052) and bit 6 in status word 2 (r0053).

f_act == f_set

Entry freq . deviat

 

 

0.00 ... 20.00 [Hz]

 

 

P2163.D (3.00)

Delay_T perm. dev.

 

 

0 ... 10000 [ms]

 

 

P2165.D (10)

f_act

+

f_set

1

0

{

 

 

 

f_act == f_set

 

0 T

 

r2197 Bit07

 

 

 

 

 

 

 

 

 

 

 

 

r0052 Bit08

 

 

 

r0053 Bit06

Hyster freq deviat

0.00 ... 10.00 [Hz] P2164.D (3.00)

Index:

 

P2164[0]

: 1st. Drive data set (DDS)

P2164[1]

: 2nd. Drive data set (DDS)

P2164[2]

: 3rd. Drive data set (DDS)

P2165[3] Delay time permitted deviation

 

Min:

0

Level

 

CStat:

CUT

Datatype: U16

Unit: ms

Def:

10

2

 

 

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

10000

 

Delay time for detecting permitted deviation of frequency from setpoint.

Index:

P2165[0] : 1st. Drive data set (DDS)

P2165[1] : 2nd. Drive data set (DDS)

P2165[2] : 3rd. Drive data set (DDS)

Details:

See diagram in P2164.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

213

Page 213
Image 213