Parameter Description

Issue 01/06

Index:

P0719[0] : 1st. Command data set (CDS)

P0719[1] : 2nd. Command data set (CDS)

P0719[2] : 3rd. Command data set (CDS)

Note:

Using parameter P0719, it is possible to select the command or setpoint sources without changing the BICO connections (this is contrary to P0700 / P1000). However, it is not possible to change the complete connection table (refer to P0700 and P1000). Using P0719, depending on the value, only the BICO parameters listed in the following table are internally overwritten - this means that these BICO parameters are inactive.

Command source:

 

 

 

 

 

 

P0719 =

 

 

 

 

0 ... 9

 

10 ... 19

 

40 ... 49

50 ... 59

60 ... 69

P0840

 

X

 

 

 

 

 

 

 

 

 

 

 

P0844

 

X

 

 

 

 

 

 

 

 

 

 

 

P0848

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P0852

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P1035

 

X

 

 

 

 

 

 

 

 

 

 

 

P1036

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P1055

 

X

 

 

 

 

 

 

 

 

 

 

 

P1056

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P1113

 

X

 

 

 

 

 

 

 

 

 

 

 

P1140

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P1141

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P1142

 

X

 

X

 

 

 

 

 

 

 

 

 

 

P1143

 

X

 

X

 

 

 

 

 

 

 

 

 

 

Setpoint source:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P0719 =

all other values

 

 

 

0, 10, 20, 40, 50, 60

 

 

 

P1070

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

X = BICO parameter active

= BICO parameter inactive

BICO connections made previously remain unchanged.

r0720

Number of digital inputs

 

Min:

-

Level

 

Datatype: U16

Unit: -

Def:

-

3

 

 

 

P-Group: COMMANDS

 

Max:

-

 

Displays number of digital inputs.

r0722

CO/BO: Binary input values

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMMANDS

 

Max:

-

Displays status of digital inputs.

Bitfields:

 

 

 

 

 

Bit00

Digital input 1

0

OFF

1

ON

Bit01

Digital input 2

0

OFF

1

ON

Bit02

Digital input 3

0

OFF

1

ON

Bit03

Digital input 4

0

OFF

1

ON

Bit04

Digital input 5

0

OFF

1

ON

Bit05

Digital input 6

0

OFF

1

ON

Bit06

Digital input 7 (via ADC 1)

0

OFF

1

ON

Bit07

Digital input 8 (via ADC 2)

0

OFF

1

ON

Level

2

Note:

Segment is lit when signal is active.

82

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 82
Image 82
Siemens 440 manual R0720 Number of digital inputs, R0722 CO/BO Binary input values, Command source, Setpoint source