Siemens 440 manual P10123 Fixed frequency, P10133 Fixed frequency, P10143 Fixed frequency

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 116
Image 116

Parameter Description

Issue 01/06

P1012[3] Fixed frequency 12

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

55.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 12.

Index:

P1012[0] : 1st. Drive data set (DDS)

P1012[1] : 2nd. Drive data set (DDS)

P1012[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

P1013[3] Fixed frequency 13

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

60.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 13.

Index:

P1013[0] : 1st. Drive data set (DDS)

P1013[1] : 2nd. Drive data set (DDS)

P1013[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

P1014[3] Fixed frequency 14

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

65.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 14.

Index:

P1014[0] : 1st. Drive data set (DDS)

P1014[1] : 2nd. Drive data set (DDS)

P1014[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

P1015[3] Fixed frequency 15

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

65.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Level

2

Defines fixed frequency setpoint 15.

Index:

P1015[0] : 1st. Drive data set (DDS)

P1015[1] : 2nd. Drive data set (DDS)

P1015[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

P1016[3] Fixed frequency mode - Bit 0

 

Min:

1

Level

 

CStat:

CT

Datatype: U16

Unit: -

Def:

1

3

 

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

3

 

Fixed frequencies can be selected in three different modes. Parameter P1016 defines the mode of selection Bit 0.

Possible Settings:

1Direct selection

2Direct selection + ON command

3Binary coded selection + ON command

Index:

P1016[0] : 1st. Command data set (CDS)

P1016[1] : 2nd. Command data set (CDS)

P1016[2] : 3rd. Command data set (CDS)

Details:

See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.

116

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 116
Image 116
Siemens 440 manual P10123 Fixed frequency, P10133 Fixed frequency, P10143 Fixed frequency, P10153 Fixed frequency