Issue 01/06

Parameter Description

3.17Fixed frequencies

P1001[3] Fixed frequency 1

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

0.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 1.

There are three options available for selection of the fixed frequencies:

1.Direct selection

2.Direct selection + ON command

3.Binary coded selection + ON command

1.Direct selection (P0701 - P0706 = 15):

-In this mode of operation 1 digital input selects 1 fixed frequency.

-If several inputs are active together, the selected frequencies are summed.

-E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.

2.Direct selection + ON command (P0701 - P0706 = 16):

-The fixed frequency selection combines the fixed frequencies with an ON command.

-In this mode of operation 1 digital input selects 1 fixed frequency.

-If several inputs are active together, the selected frequencies are summed.

-E.g.: FF1 + FF2 + FF3 + FF4 + FF5 + FF6.

3.Binary coded selection + ON command (P0701 - P0706 = 17):

-Up to 16 fixed frequencies can be selected using this method.

-The fixed frequencies are selected according to the following table:

Index:

P1001[0] : 1st. Drive data set (DDS)

P1001[1] : 2nd. Drive data set (DDS)

P1001[2] : 3rd. Drive data set (DDS)

Example:

Binary coded selection :

 

 

DIN4

DIN3

DIN2

DIN1

0 Hz

FF0

0

0

0

0

P1001

FF1

0

0

0

1

P1002

FF2

0

0

1

0

P1003

FF3

0

0

1

1

P1004

FF4

0

1

0

0

P1005

FF5

0

1

0

1

P1006

FF6

0

1

1

0

P1007

FF7

0

1

1

1

P1008

FF8

1

0

0

0

P1009

FF9

1

0

0

1

P1010

FF10

1

0

1

0

P1011

FF11

1

0

1

1

P1012

FF12

1

1

0

0

P1013

FF13

1

1

0

1

P1014

FF14

1

1

1

0

P1015

FF15

1

1

1

1