Parameter Description | Issue 01/06 |
P2104[3] BI: 2. Faults acknowledgement |
| Min: | 0:0 | ||
CStat: | CT | Datatype: U32 | Unit: - | Def: | 0:0 |
COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Selects second source of fault acknowledgement.
Index:
P2104[0] : 1st. Command data set (CDS)
P2104[1] : 2nd. Command data set (CDS)
P2104[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Level
3
P2106[3] | BI: External fault |
|
| Min: | 0:0 | |
| CStat: | CT | Datatype: U32 | Unit: - | Def: | 1:0 |
| COMMANDS | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Selects source of external faults.
Index:
P2106[0] : 1st. Command data set (CDS)
P2106[1] : 2nd. Command data set (CDS)
P2106[2] : 3rd. Command data set (CDS)
Common Settings:
722.0= Digital input 1 (requires P0701 to be set to 99, BICO)
722.1= Digital input 2 (requires P0702 to be set to 99, BICO)
722.2= Digital input 3 (requires P0703 to be set to 99, BICO)
722.3= Digital input 4 (requires P0704 to be set to 99, BICO)
722.4= Digital input 5 (requires P0705 to be set to 99, BICO)
722.5= Digital input 6 (requires P0706 to be set to 99, BICO)
722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)
722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)
Level
3
r2110[4] | Warning number |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
| Max: | - |
Displays warning information.
Level
2
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be viewed.
Index:
r2110[0] : Recent Warnings
r2110[1] : Recent Warnings
r2110[2] : Recent Warnings
r2110[3] : Recent Warnings
Note:
-Indices 0 and 1 are not stored.
-The keypad will flash while a warning is active. The LEDs indicate the warning status in this case.
-If an AOP is in use, the display will show number and text of the active warning.
P2111 | Total number of warnings |
| Min: | 0 | ||
| CStat: | CT | Datatype: U16 | Unit: - | Def: | 0 |
| ALARMS | Active: first confirm | QuickComm.: No | Max: | 4 |
Level
3
Displays number of warning (up to 4) since last reset. Set to 0 to reset the warning history.
208 | MICROMASTER 440 Parameter List |