Issue 01/06

Parameter Description

P2866

Mode timer 4

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

13

Level

3

Selects mode of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.

Possible Settings:

0ON delay (seconds)

1OFF delay (seconds)

2ON/OFF delay (seconds)

3Pulse generator (seconds)

10ON delay (minutes)

11OFF delay (minutes)

12ON/OFF delay (minutes)

13Pulse generator (minutes)

Dependency:

P2802[3] is active level for the timer.

r2867

BO: Timer 4

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: TECH

 

Max:

-

Level

3

Displays output of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.

Dependency:

P2802[3] is active level for the timer.

r2868

BO: Nout timer 4

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: TECH

 

Max:

-

Level

3

Displays Not-output of timer 4. P2864, P2865, P2866 are the inputs of the timer, outputs are P2867, P2868.

Dependency:

P2802[3] is active level for the timer.

P2869[2] CI: ADD 1

 

 

Min:

0:0

CStat:

CUT

Datatype: U32

Unit: -

Def:

755:0

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

4000:0

Define inputs of Adder 1, result is in P2870.

Level

3

 

 

P2800

P2802[4]

 

 

 

 

 

 

 

 

P2869

x

 

 

 

 

200%

Index 0

1

 

 

 

 

 

Result

Index 1

x

 

 

 

 

 

2

 

 

 

 

 

-200%

 

 

 

 

 

 

 

 

 

 

 

x1 + x2

 

Index:

P2869[0] : Connector input 0 (CI 0)

P2869[1] : Connector input 1 (CI 1)

Dependency:

P2802[4] is the active level for the Adder.

 

Result = x1 + x2

 

 

r2870

 

 

 

If:

x1 + x2 >

Result = 200%

 

200%

 

 

 

x1 + x2 < -200%

Result = -200%

r2870

CO: ADD 1

 

Min:

-

 

Datatype: Float

Unit: %

Def:

-

 

P-Group: TECH

 

Max:

-

Level

3

Result of Adder 1.

Dependency:

P2802[4] is active level for the Adder.

P2871[2] CI: ADD 2

 

 

Min:

0:0

CStat:

CUT

Datatype: U32

Unit: -

Def:

755:0

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Define inputs of Adder 2, result is in P2872.

Index:

P2871[0] : Connector input 0 (CI 0)

P2871[1] : Connector input 1 (CI 1)

Dependency:

P2802[5] is active level for the Adder.

r2872

CO: ADD 2

 

Min:

-

 

Datatype: Float

Unit: %

Def:

-

 

P-Group: TECH

 

Max:

-

Result of Adder 2.

Dependency:

P2802[5] is active level for the Adder.

MICROMASTER 440 Parameter List 6SE6400-5BB00-0BP0