Issue 01/06

Parameters

2.2Quick commissioning (P0010 = 1)

The following parameters are necessary for quick commissioning (P0010 = 1).

Quick commissioning (P0010 = 1)

Par.-No.

Name

Access level

Cstat

P0100

Europe / North America

1

C

P0205

Inverter application

3

C

P0300

Select motor type

2

C

P0304

Motor voltage rating

1

C

P0305

Motor current rating

1

C

P0307

Motor power rating

1

C

P0308

Motor cosPhi rating

1

C

P0309

Motor efficiency rating

1

C

P0310

Motor frequency rating

1

C

P0311

Motor speed rating

1

C

P0320

Motor magnetizing current

3

CT

P0335

Motor cooling

2

CT

P0640

Motor overload factor [%]

2

CUT

P0700

Selection of command source

1

CT

P1000

Selection of frequency setpoint

1

CT

P1080

Min. speed

1

CUT

P1082

Max. speed

1

CT

P1120

Ramp-up time

1

CUT

P1121

Ramp-down time

1

CUT

P1135

OFF3 ramp-down time

2

CUT

P1300

Control mode

2

CT

P1500

Selection of torque setpoint

2

CT

P1910

Select motor data identification

2

CT

P1960

Speed control optimisation

3

CT

P3900

End of quick commissioning

1

C

When P0010 = 1 is chosen, P0003 (user access level) can be used to select the parameters to be accessed. This parameter also allows selection of a user-defined parameter list for quick commissioning.

At the end of the quick commissioning sequence, set P3900 = 1 to carry out the necessary motor calculations and clear all other parameters (not included in P0010 = 1) to their default settings.

Note

This applies only in Quick Commissioning mode.

Reset to Factory default

To reset all parameters to the factory default settings; the following parameters should be set as follows:

Set P0010 = 30

Set P0970 = 1

Note

The reset process takes approximately 10 seconds to complete. Reset to Factory default

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

15

Page 15
Image 15
Siemens 440 manual Quick commissioning P0010 =, Reset to Factory default