Issue 01/06

Parameter Description

P1470[3] Gain speed controller (SLVC)

 

Min:

0.0

CStat:

CUT

Datatype: Float

Unit: -

Def:

3.0

P-Group:

CONTROL

Active: Immediately

QuickComm.: No

Max:

2000.0

Enters gain of speed controller for sensorless vector control (SLVC).

Level

2

P1492

 

r1490

 

0

1

0

P1488

P1489

150 ms

Droop

P1496 P0341 P0342

 

r1518

 

Precontrol

 

P1470

P1472

r1170

r1084

r1438

Kp

Tn

 

Freq. setpoint

r0063

Act. frequency

from observer model

Index:

*)

 

 

 

Torque

 

 

P1452

r0064

setpoint

 

 

r1508

r0079

 

*) only active , if pre-control is enabled

 

 

(P1496 > 0)

 

P1470[0]

:

1st. Drive data set (DDS)

P1470[1]

:

2nd. Drive data set (DDS)

P1470[2]

:

3rd. Drive data set (DDS)

P1472[3] Integral time n-ctrl. (SLVC)

 

Min:

25

Level

 

CStat:

CUT

Datatype: U16

Unit: ms

Def:

400

2

 

 

 

P-Group:

CONTROL

Active: Immediately

QuickComm.: No

Max:

32001

 

Enters integral time of speed controller for sensorless vector control (SLVC).

Index:

P1472[0] : 1st. Drive data set (DDS)

P1472[1] : 2nd. Drive data set (DDS)

P1472[2] : 3rd. Drive data set (DDS)

P1477[3] BI: Set integrator of n-ctrl.

 

Min:

0:0

CStat:

CUT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

CONTROL

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Selects source to read in command to enable speed controller.

Index:

P1477[0] :

1st. Command data set (CDS)

P1477[1]

:

2nd. Command data set (CDS)

P1477[2]

:

3rd. Command data set (CDS)

P1478[3] CI: Set integrator value n-ctrl.

 

Min:

0:0

Level

 

CStat:

UT

Datatype: U32

Unit: -

Def:

0:0

3

 

 

 

P-Group:

CONTROL

Active: first confirm

QuickComm.: No

Max:

4000:0

 

Selects source for integral part of speed controller.

Index:

P1478[0] : 1st. Command data set (CDS)

P1478[1] : 2nd. Command data set (CDS)

P1478[2] : 3rd. Command data set (CDS)

Dependency:

In case of sensorless vector control, integrator freezing must be selected (Bit 1 "Integral freeze (SLVC)" of P1400 has to be set) to save the integrator output.

Note:

-If the setting command is not connected (P1477=0), a pending value is read in after pulse enable at the end of the excitation time (P0346) and the integral component of the speed controller is set once.

-If the P1482 (integral component of speed controller) is connected upon pulse enable, the integral component of the controller is set to the last value prior the pulse inhibit.

-Neither function works after flying start.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

169

Page 169
Image 169
Siemens 440 P14703 Gain speed controller Slvc, P14723 Integral time n-ctrl. Slvc, P14773 BI Set integrator of n-ctrl, 169