Parameter Description | Issue 01/06 |
P1076[3] | CI: Additional setpoint scaling |
| Min: | 0:0 | ||
| CStat: | CT | Datatype: U32 | Unit: - | Def: | 1:0 |
| SETPOINT | Active: first confirm | QuickComm.: No | Max: | 4000:0 |
Level
3
Defines source of scaling for additional setpoint (to be added to main setpoint).
Index:
P1076[0] : 1st. Command data set (CDS)
P1076[1] : 2nd. Command data set (CDS)
P1076[2] : 3rd. Command data set (CDS)
Common Settings:
1= Scaling of 1.0 (100%)
755= Analog input 1 Setpoint
1024 = Fixed Frequency Setpoint
1050 = MOP Setpoint
r1078 | CO: Total frequency setpoint |
| Min: | - |
| Datatype: Float | Unit: Hz | Def: | - |
|
| Max: | - |
Displays sum of main and additional setpoints in [Hz].
Level
3
r1079 | CO: Selected frequency setpoint |
| Min: | - |
| Datatype: Float | Unit: Hz | Def: | - |
|
| Max: | - |
Displays selected frequency setpoint.
Level
3
Following frequency setpoints are displayed:
-r1078 Total frequency setpoint
-P1058 JOG frequency right
-P1059 JOG frequency left
Dependency:
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG left respectively.
Note:
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
126 | MICROMASTER 440 Parameter List |