Parameter Description

Issue 01/06

P1076[3]

CI: Additional setpoint scaling

 

Min:

0:0

 

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

 

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines source of scaling for additional setpoint (to be added to main setpoint).

Index:

P1076[0] : 1st. Command data set (CDS)

P1076[1] : 2nd. Command data set (CDS)

P1076[2] : 3rd. Command data set (CDS)

Common Settings:

1= Scaling of 1.0 (100%)

755= Analog input 1 Setpoint

1024 = Fixed Frequency Setpoint

1050 = MOP Setpoint

r1078

CO: Total frequency setpoint

 

Min:

-

 

Datatype: Float

Unit: Hz

Def:

-

 

P-Group: SETPOINT

 

Max:

-

Displays sum of main and additional setpoints in [Hz].

Level

3

r1079

CO: Selected frequency setpoint

 

Min:

-

 

Datatype: Float

Unit: Hz

Def:

-

 

P-Group: SETPOINT

 

Max:

-

Displays selected frequency setpoint.

Level

3

Following frequency setpoints are displayed:

-r1078 Total frequency setpoint

-P1058 JOG frequency right

-P1059 JOG frequency left

Dependency:

P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG left respectively.

Note:

P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.

126

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 126
Image 126
Siemens 440 P10763 CI Additional setpoint scaling, R1078 CO Total frequency setpoint, R1079 CO Selected frequency setpoint