Issue 01/06Faults and Alarms

F0041 Failure, motor data identification

STOP II

Quit

Refer to F0001

Cause

Motor data identification run unsuccessful (refer to fault value r0949):

-r0949 = 0: Load missing.

-r0949 = 1: Current limit was reached during the identification run.

-r0949 = 2: Identified stator resistance less than 0.1% or greater than 100%.

-r0949 = 3: Identified rotor resistance less than 0.1% or greater than 100%.

-r0949 = 4: Identified stator reactance less than 50% or greater than 500%

-r0949 = 5: Identified magnetizing reactance less than 50% or greater than 500%

-r0949 = 6: Identified rotor time constant less than 10ms or greater than 5s

-r0949 = 7: Identified total leakage reactance less than 5% or greater than 50%

-r0949 = 8: Identified stator leakage reactance less than 25% or greater than 250%

-r0949 = 9: Identified rotor leakage reactance less than 25% or greater than 250%

-r0949 = 20: Identified IGBT response voltage less than 0.5 or greater than 10V

-r0949 = 30: Current controller at voltage limit value

-r0949 = 40: Identified data set inconsistent; at least one identification run unsuccessful

NOTE

Percentage values based on the impedence Zb = Vmot,rated / sqrt(3) / Imot,rated

Diagnosis & Remedy

Please check the following:

-r0949 = 0: Is the motor connected to the inverter ?

-r0949 = 1-40: Is the motor data in P0304-P0311 correct ?

-r0949 = 1-40: Motor circuit configuration correct (star, delta configuration) ?

F0042 Fault/error when optimizing the speed controller

STOP II

Quit

Refer to F0001

Cause

Automatic data identification run unsuccessful (refer to fault value r0949):

-r0949 = 0: Time slice overflow while waiting for a stable speed

-r0949 = 1: No matching/appropriate value when reading

F0051 Parameter EEPROM fault

STOP II

Quit

Refer to F0001

Cause

-read or write operation while saving parameters in the EEPROM was unsuccessful.

Diagnosis & Remedy

-reset to factory setting and then re-parameterize

-if required, change the drive

F0052 Power stack fault

STOP II

Quit

Refer to F0001

Cause

-read error, power data or invalid power module data.

Diagnosis & Remedy

-change the drive

F0053 I/O EEPROM fault

STOP II

Quit

Refer to F0001

Cause

-fault with I/O EEPROM read operation or invalid data.

Diagnosis & Remedy

Please check the following:

-check I/O data and if required repeat the operation

-the installation of the I/O module in the inverter if required, replace the I/O module

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

311

Page 311