Parameter Description

Issue 01/06

P1133[3] Ramp-down final rounding time

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: s

Def:

0.00

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

40.00

Defines rounding time at end of ramp-down as shown in P1130 (ramp-up initial rounding time).

Index:

P1133[0] : 1st. Drive data set (DDS)

P1133[1] : 2nd. Drive data set (DDS)

P1133[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1130.

Level

2

P1134[3] Rounding type

 

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

1

Level

2

Defines the smoothing which is active by setpoint modifications during acceleration or deceleration (e.g. new setpoint, OFF1, OFF3, REV).

This smoothing is applied, if the motor is ramped-up or ramped-down and

-P1134 = 0,

-P1132 > 0, P1133 > 0 and

-the setpoint is not yet reached.

P1132 > 0, P1133 > 0

f

fSet Setpoint reached

Setpoint not reached

P1134 = 0

t

P1132

P1133

P1132

P1133

f

Setpoint reached

fSet

Setpoint not reached

P1134 = 1

 

 

t

P1132

P1133

P1133

ON

 

 

OFF1

 

t

Possible Settings:

0Continuous smoothing

1Discontinuous smoothing

Index:

P1134[0] : 1st. Drive data set (DDS)

P1134[1] : 2nd. Drive data set (DDS)

P1134[2] : 3rd. Drive data set (DDS)

Dependency:

No effect until P1132 (Ramp-down initial rounding time) or P1133 (Ramp-down final rounding time) > 0 s.

134

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 134
Image 134
Siemens 440 manual P11333 Ramp-down final rounding time, P11343 Rounding type, P1132 0, P1133, P1134 =