Siemens 440 Inverter parameters HW, P0100 Europe / North America, P0199 Equipment system number

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 42
Image 42

Parameter Description

Issue 01/06

3.3Inverter parameters (HW)

P0100

Europe / North America

 

 

Min:

0

 

CStat:

C

Datatype: U16

Unit: -

Def:

0

 

P-Group:

QUICK

Active: first confirm

QuickComm.: Yes

Max:

2

Level

1

Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp].

The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082) are also set automatically here, in addition to reference frequency (P2000).

Possible

Settings:

 

0

Europe [kW],

frequency default 50 Hz

1North America [hp], frequency default 60 Hz

2North America [kW], frequency default 60 Hz

Dependency:

Where:

- Stop drive first (i.e. disable all pulses) before you change this parameter.

- P0100 can only be changed when P0010 = 1 (Commissioning mode) via the respective Commissioing interface (e.g. BOP).

- Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (see P0340 - calculation of motor parameters).

Changing P0100 overwrites the settings of the DIP50/60 switch (location shown in the diagram below):

1.Parameter P0100 has an higher priority than the DIP50/60 switch.

2.However, after the inverter is powered-on again and P0100 < 2, the DIP50/60 setting will take priority and overwrite P0100.

3.The DIP50/60 switch does not have any effect, if P0100 = 2.

Remove I/O board

DIP50/60

Power

 

 

Quick

 

 

commissioning

cycle

 

 

 

 

P0010 = 1

 

 

 

P0100 = 2

yes

yes

P0100 = 2

 

 

?

 

 

?

no

 

 

no

 

 

no

P0100 = 1

 

 

 

 

 

 

?

DIP50/60 =

no

 

yes

 

 

50 Hz

 

 

 

?

 

 

 

yes

 

 

 

Power in kW

 

Power in kW

 

Power in hp

Frequency 50 Hz

 

Frequency 60 Hz

 

Frequency 60 Hz

 

 

 

 

 

P0100 = 0

 

P0100 = 2

 

P0100 = 1

Notice:

P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see diagram above).

P0199

Equipment system number

 

Min:

0

 

CStat:

UT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

-

Active: first confirm

QuickComm.: No

Max:

255

Equipment system number This parameter has no operation effect.

Level

2

42

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 42