Parameter Description

Issue 01/06

r2090

BO: Control word 1 from CB

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMM

 

Max:

-

Displays control word 1 received from communication board (CB).

Bitfields:

 

 

 

 

 

Bit00

ON/OFF1

0

NO

1

YES

Bit01

OFF2: Electrical stop

0

YES

1

NO

Bit02

OFF3: Fast stop

0

YES

1

NO

Bit03

Pulses enabled

0

NO

1

YES

Bit04

RFG enable

0

NO

1

YES

Bit05

RFG start

0

NO

1

YES

Bit06

Setpoint enable

0

NO

1

YES

Bit07

Fault acknowledge

0

NO

1

YES

Bit08

JOG right

0

NO

1

YES

Bit09

JOG left

0

NO

1

YES

Bit10

Control from PLC

0

NO

1

YES

Bit11

Reverse (setpoint inversion)

0

NO

1

YES

Level

3

Bit13

Motor

potentiometer

MOP

up

0

NO

1

YES

Bit14

Motor

potentiometer

MOP

down

0

NO

1

YES

Bit15

CDS Bit 0 (Local/Remote)

0

NO

1

YES

Details:

See relevant communication board manual for protocol definition and appropriate settings.

r2091

BO: Control word 2 from CB

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMM

 

Max:

-

Displays control word 2 received from communication board (CB).

Bitfields:

 

 

 

 

 

Bit00

Fixed frequency Bit 0

0

NO

1

YES

Bit01

Fixed frequency Bit 1

0

NO

1

YES

Bit02

Fixed frequency Bit 2

0

NO

1

YES

Bit03

Fixed frequency Bit 3

0

NO

1

YES

Bit04

Drive data set (DDS) Bit 0

0

NO

1

YES

Bit05

Drive data set (DDS) Bit 1

0

NO

1

YES

Bit08

PID enabled

0

NO

1

YES

Bit09

DC brake enabled

0

NO

1

YES

Level

3

Bit11

Droop enabled

0

NO

1

YES

Bit12

Torque control

0

NO

1

YES

Bit13

External fault 1

0

YES

1

NO

Bit15

Command data set (CDS) Bit 1

0

NO

1

YES

Details:

See relevant communication board manual for protocol definition and appropriate settings.

206

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 206