Issue 01/06

P2849

BI: Timer 1

 

 

Min:

0:0

 

CStat:

CUT

Datatype: U32

Unit: -

Def:

0:0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Define input signal of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.

 

 

P2850 (0.000)

P2851(0)

 

 

 

P2800 P2802.0

Delay Time

 

Mode

 

 

 

ON Delay

0

 

 

 

 

T

0

 

 

 

 

 

 

 

 

 

OFF Delay

1

 

 

 

I

0

T

 

 

P2849

 

Ou

 

 

 

 

 

Index0

n

ON/OFF Delay

2

t

r2852

 

 

T

T

NOu

 

 

 

 

 

 

 

Pulse Gernerator

 

1t

r2853

 

 

3

 

 

 

 

 

T

 

 

 

 

 

 

 

 

In

 

 

 

 

Out

 

 

 

t

 

 

 

 

P2851

= 0

(ON Delay)

 

 

 

 

P2850

 

t

 

 

 

 

P2851

= 1

(OFF Delay)

 

 

 

 

 

P2850

t

 

 

 

 

P2851

= 2

(ON-OFF Delay)

 

 

 

 

P2850

P2850

t

 

 

 

P2851

= 3

(Pulse Generator)

 

 

In

Out

P2850

In

Out

P2850

Dependency:

P2802[0] is active level for the timer.

t

t

t

t

P2850

Delay time of timer 1

 

 

Min:

0.0

 

CStat:

CUT

Datatype: Float

Unit: -

Def:

0.0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

9999.9

Level

3

Defines delay time of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.

Dependency:

P2802[0] is active level for the timer.

250

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 250
Image 250