Issue 01/06

Parameter Description

P0364[3] Magnetizing curve flux 3

 

Min:

0.0

CStat:

CUT

Datatype: Float

Unit: %

Def:

115.0

P-Group:

MOTOR

Active: Immediately

QuickComm.: No

Max:

300.0

Level

4

Specifies third flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).

Index:

P0364[0] : 1st. Drive data set (DDS)

P0364[1] : 2nd. Drive data set (DDS)

P0364[2] : 3rd. Drive data set (DDS)

Details:

See P0362 (magnetizing curve flux 1).

P0365[3] Magnetizing curve flux 4

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: %

Def:

125.0

4

 

 

 

P-Group:

MOTOR

Active: Immediately

QuickComm.: No

Max:

300.0

 

Specifies fourth flux value of saturation characteristic in [%] relative to rated motor voltage (P0304).

Index:

P0365[0] : 1st. Drive data set (DDS)

P0365[1] : 2nd. Drive data set (DDS)

P0365[2] : 3rd. Drive data set (DDS)

Details:

See P0362 (magnetizing curve flux 1).

P0366[3] Magnetizing curve imag 1

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: %

Def:

50.0

4

 

P-Group:

MOTOR

Active: Immediately

QuickComm.: No

Max:

500.0

 

Specifies first magnetizing current value of the saturation characteristic in [%] relative to the rated magnetizing current (P0331).

Index:

P0366[0] : 1st. Drive data set (DDS)

P0366[1] : 2nd. Drive data set (DDS)

P0366[2] : 3rd. Drive data set (DDS)

Dependency:

Affects P0320 (motor magnetizing current).

Details:

See P0362 (magnetizing curve flux 1).

P0367[3] Magnetizing curve imag 2

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: %

Def:

75.0

4

 

P-Group:

MOTOR

Active: Immediately

QuickComm.: No

Max:

500.0

 

Specifies second magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current (P0331).

Index:

P0367[0] : 1st. Drive data set (DDS)

P0367[1] : 2nd. Drive data set (DDS)

P0367[2] : 3rd. Drive data set (DDS)

Dependency:

Affects P0320 (motor magnetizing current).

Details:

See P0362 (magnetizing curve flux 1).

P0368[3] Magnetizing curve imag 3

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: %

Def:

135.0

4

 

 

 

P-Group:

MOTOR

Active: Immediately

QuickComm.: No

Max:

500.0

 

Specifies third magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current (P0331).

Index:

P0368[0] : 1st. Drive data set (DDS)

P0368[1] : 2nd. Drive data set (DDS)

P0368[2] : 3rd. Drive data set (DDS)

Dependency:

Affects P0320 (motor magnetizing current).

Details:

See P0362 (magnetizing curve flux 1).

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

63

Page 63
Image 63