Siemens 440 manual P1210 Automatic restart, 139

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 139
Image 139

Issue 01/06

Parameter Description

3.23Automatic restart

P1210

Automatic restart

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

1

 

P-Group:

FUNC

Active: first confirm

QuickComm.: No

Max:

6

Level

2

Configures automatic restart function

 

Possible Settings:

 

0

Disabled

 

1

Trip reset after power on,

P1211 disabled

2

Restart after mains blackout,

P1211 disabled

3

Restart after mains brownout or fault,

P1211 enabled

4

Restart after mains brownout,

P1211 enabled

5

Restart after mains blackout and fault,

P1211 disabled

6

Restart after mains brown- /blackout or fault

P1211 disabled

Dependency:

Automatic restart requires constant ON command via a digital input wire link.

Caution:

P1210 > 2 can cause the motor to restart automatically without toggling the ON command !

Notice:

A "mains brownout" is where the power in interrupted and re-applied before the display on the BOP (if one is fitted to the inverter) has gone dark (a very short mains break where the DC link has not fully collapsed).

A "mains blackout" is where the display has gone dark (a long mains break where the DC link has fully collapsed) before the power is re-applied.

P1210 = 0:

Automatic restart is disabled.

P1210 = 1:

The inverter will acknowledge (reset) faults i.e. it will reset a fault when the is re-applied. This means the inverter must be fully powered down, a brownout is not sufficed. The inverter will not run until the ON command has been toggled.

P1210 = 2:

The inverter will acknowledge the fault F0003 at power on after blackout and restarts the drive. It is necessary that the ON command is wired via digital input (DIN).

P1210 = 3:

For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the faults (F0003, etc.). The inverter will acknowledge the fault and restarts the drive after a blackout or bronwout. It is necessary that the ON command is wired via digital input (DIN).

P1210 = 4:

For these settings it is fundamental that the drive only restarts if it has been in a RUN state at the time of the fault (F0003). The inverter will acknowledge the fault and restarts the drive after a blackout or bronwout. It is necessary that the ON command is wired via digital input (DIN).

P1210 = 5:

The inverter will acknowledge the faults F0003 etc. at power on after blackout and restarts the drive. It is necessary that the ON command is wired via digital input (DIN).

P1210 = 6:

The inverter will acknowledge the faults (F0003 etc.) at power on after blackout or brownout and restarts the drive. It is necessary that the ON command is wired via digital input (DIN). Setting 6 causes the motor to restart immediately.

Following table presents an overview of parameter P1210 and its functionality.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

139

Page 139
Image 139
Siemens 440 manual P1210 Automatic restart, 139