Issue 01/06

Parameter Description

P1135[3] OFF3 ramp-down time

 

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: s

Def:

5.00

P-Group:

SETPOINT

Active: first confirm

QuickComm.: Yes

Max:

650.00

Defines ramp-down time from maximum frequency to standstill for OFF3 command.

Level

2

 

OFF3

 

t

 

 

f

 

 

 

 

 

 

 

 

 

f max

 

 

f act,motor

 

(P1082)

 

 

 

 

 

f 2

 

P2168

 

 

 

 

 

f

act,inverter

 

 

 

 

 

P2167

 

 

 

 

 

0

P2168

 

t

 

 

 

 

tdown,OFF3 =

P1135

f 2

 

tdown,OFF3

 

P1082

 

 

 

 

 

r0052 Bit02

P1135

 

 

 

 

 

 

 

 

 

Operation

Pulse cancellation

t

Index:

P1135[0] : 1st. Drive data set (DDS)

P1135[1] : 2nd. Drive data set (DDS)

P1135[2] : 3rd. Drive data set (DDS)

Note:

This time may be exceeded if the VDC_max. level is reached.

P1140[3] BI: RFG enable

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines command source of RFG enable command (RFG: ramp function generator). If binary input is equal to zero then the RFG output will be set immediately to 0.

Index:

P1140[0] : 1st. Command data set (CDS)

P1140[1] : 2nd. Command data set (CDS)

P1140[2] : 3rd. Command data set (CDS)

P1141[3] BI: RFG start

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal to zero then the RFG output is held at it present value.

Index:

P1141[0] :

1st. Command data set (CDS)

P1141[1]

:

2nd. Command data set (CDS)

P1141[2]

:

3rd. Command data set (CDS)

P1142[3] BI: RFG enable setpoint

 

 

Min:

0:0

Level

 

CStat:

CT

Datatype: U32

Unit: -

Def:

1:0

3

 

 

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

 

Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary input is equal to zero then the RFG input will be set to zero and the RFG output will be ramp-down to zero.

Index:

P1142[0] : 1st. Command data set (CDS)

P1142[1] : 2nd. Command data set (CDS)

P1142[2] : 3rd. Command data set (CDS)

r1170

CO: Frequency setpoint after RFG

 

Min:

-

Level

 

Datatype: Float

Unit: Hz

Def:

-

3

 

 

 

P-Group: SETPOINT

 

Max:

-

 

Displays overall frequency setpoint after ramp generator.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

135

Page 135
Image 135