Siemens 440 manual P00143 Store mode, Store request via USS/CB, Value of P0014x, Result

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 28
Image 28

Parameter Description

Issue 01/06

Index:

P0013[0] : 1st user parameter

P0013[1] : 2nd user parameter

P0013[2] : 3rd user parameter

P0013[3] : 4th user parameter

P0013[4] : 5th user parameter

P0013[5] : 6th user parameter

P0013[6] : 7th user parameter

P0013[7] : 8th user parameter

P0013[8] : 9th user parameter

P0013[9] : 10th user parameter

P0013[10] : 11th user parameter

P0013[11] : 12th user parameter

P0013[12] : 13th user parameter

P0013[13] : 14th user parameter

P0013[14] : 15th user parameter

P0013[15] : 16th user parameter

P0013[16] : 17th user parameter

P0013[17] : 18th user parameter

P0013[18] : 19th user parameter

P0013[19] : 20th user parameter

Dependency:

First, set P0011 ("lock") to a different value than P0012 ("key") to prevent changes to user-defined parameter. Then, set P0003 to 0 to activate the user-defined list.

When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").

Note:

-Alternatively, set P0010 = 30 (commissioning parameter filter = factory setting) and P0970 = 1 (factory reset) to perform a complete factory reset.

-The default values of P0011 ("lock") and P0012 ("key") are the same.

P0014[3]

Store mode

 

 

Min:

0

 

CStat:

UT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

-

Active: first confirm

QuickComm.: No

Max:

1

Level

3

Sets the store mode for parameters ("volatile" (RAM) or "nonvolatile" (EEPROM)).

Possible Settings:

0Volatile (RAM)

1Nonvolatile (EEPROM)

Index:

P0014[0] : Serial interface COM link

P0014[1] : Serial interface BOP link

P0014[2] : PROFIBUS / CB

Note:

1.With the BOP the parameter will always be stored in the EEPROM.

2.P0014 itself will always be stored in the EEPROM.

3.P0014 will not be changed by performing a factory reset (P0010 = 30 and P0971 = 1).

4.P0014 can be transferred during a DOWNLOAD (P0010 = 29).

5.If "Store request via USS/CB = volatile (RAM)" and "P0014[x] = volatile (RAM)", you can make a transfer of all parameter values into the nonvolatile memory via P0971.

6.If "Store request via USS/CB" and P0014[x] are not consistent, the setting of P14[x] = "store nonvolatile (EEPROM)" has always higher priority.

Store request via USS/CB

EEPROM

EEPROM

RAM

RAM

Value of P0014[x]

RAM

EEPROM

RAM

EEPROM

Result

EEPROM

EEPROM

RAM

EEPROM

28

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 28
Image 28