Parameter Description

Issue 01/06

Direct selection of FF P1001 via DIN 1:

P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1

P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1

P1016

 

 

P1020

1

DIN1

r0722.0

 

 

 

 

 

0

2,3

 

 

 

DIN2

P1021

r0722.1

0

. . . .

P1017

0

 

1

P1001

 

2,3

 

 

0

 

P1002

+

+

. . .

r1024

Dependency:

Select fixed frequency operation (using P1000).

Inverter requires ON command to start in the case of direct selection (P0701 - P0706 = 15).

Note:

Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.

P1002[3] Fixed frequency 2

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

5.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 2.

Index:

P1002[0] : 1st. Drive data set (DDS)

P1002[1] : 2nd. Drive data set (DDS)

P1002[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

P1003[3] Fixed frequency 3

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

10.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 3.

Index:

P1003[0] : 1st. Drive data set (DDS)

P1003[1] : 2nd. Drive data set (DDS)

P1003[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

P1004[3] Fixed frequency 4

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

15.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 4.

Index:

P1004[0] : 1st. Drive data set (DDS)

P1004[1] : 2nd. Drive data set (DDS)

P1004[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

P1005[3] Fixed frequency 5

 

 

Min:

-650.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

20.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Defines fixed frequency setpoint 5.

Index:

P1005[0] : 1st. Drive data set (DDS)

P1005[1] : 2nd. Drive data set (DDS)

P1005[2] : 3rd. Drive data set (DDS)

Details:

See parameter P1001 (fixed frequency 1).

Level

2

114

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 114
Image 114
Siemens 440 manual P10023 Fixed frequency, P10033 Fixed frequency, P10043 Fixed frequency, P10053 Fixed frequency, 114