Issue 01/06

Parameter Description

The actual active command data set (CDS) is displayed in parameter r0050.

 

selected

active

 

CDS

CDS

 

r0055

r0054

r0050

 

Bit15

Bit15

 

1. CDS

0

0

0

 

 

 

 

2. CDS

0

1

1

3. CDS

1

0

2

3. CDS

1

1

2

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

Example:

Typical procedure for CDS switch-over:

- CDS1: Command source via terminal and setpoint source via analog input (ADC)

- CDS2: Command source via BOP and setpoint source via MOP - CDS switch-over takes place via digital input 4 (DIN 4)

Steps:

1.Perform commissioning with CDS1 parameters (P0700[0] = 2 and P1000[0] = 2)

2.Connect P0810 (P0811 if necessary) with the source of CDS switch-over (P0704[0] = 99, P0810 = 722.3)

3.Copy CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2)

4.Change CDS2 parameter as required (set parameters for CDS2 [P0700=1 and P1000=1])

DIN4

P0810 = 722.3

Terminals

BOP

ADC

MOP

P0700[0] = 2

0

P0700[1] = 1

1

P1000[0] = 2

0

P1000[1] = 1

1

Sequence control

Setpoint

 

 

Motor

channel

 

 

control

 

 

 

 

 

 

Note:

P0811 is also relevant for command data set (CDS) set selection.

P0811

BI: CDS bit 1

 

 

Min:

0:0

 

CStat:

CUT

Datatype: U32

Unit: -

Def:

0:0

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4095:0

Level

2

Selects command source from which to read Bit 1 for selecting a command data set (see P0810).

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

Note:

P0810 is also relevant for command data set (CDS) selection.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

99

Page 99
Image 99