Parameter Description | Issue 01/06 |
P0927 | Parameter changeable via |
| Min: | 0 | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 15 |
| COMM | Active: first confirm | QuickComm.: No | Max: | 15 |
Specifies the interfaces which can be used to change parameters.
Level
2
This parameter allows the user to easily protect the inverter from unauthorized modification of parameters. Annotation: Parameter P0927 is not password protected.
Bitfields: |
|
|
|
|
|
|
Bit00 | PROFIBUS / | CB | 0 | NO | 1 | YES |
Bit01 | BOP |
| 0 | NO | 1 | YES |
Bit02 | USS on BOP | link | 0 | NO | 1 | YES |
Bit03 | USS on COM | link | 0 | NO | 1 | YES |
Example:
Bits 0, 1, 2 and 3 set:
The default setting allows parameters to be changed via any interface. If all bits are set, the parameter is displayed on BOP as follows:
BOP:
P0927
Bits 0, 1, 2 and 3 reset:
This setting allows no parameters to be modified via any interface with the exception of P0003 and P0927. If all bits are reset, the parameter is displayed on BOP as follows:
BOP:
P0927
Details:
The
r0947[8] | CO: Last fault code |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
|
| Max: | - |
Level
2
Displays fault history according to the diagram below where:
-"F1" is the first active fault (not yet acknowledged).
-"F2" is the second active fault (not yet acknowledged).
-"F1e" is the occurrence of the fault acknowledgement for F1 & F2.
This moves the value in the 2 indices down to the next pair of indices, where they are stored. Indices 0 & 1 contain the active faults. When faults are acknowledged, indices 0 & 1 are reset to 0.
r0947[0] F1 r0947[1]
Active
F2 Fault Codes
F1e
r0947[2]
r0947[3]
F1e
r0947[4]
r0947[5]
F1e
r0947[6]
r0947[7]
Index:
F1e
F1e
F1e
Most recent Fault Codes - 1
Most recent Fault Codes - 2
Most recent Fault Codes - 3
r0947[0] : Recent fault trip
r0947[1] : Recent fault trip
r0947[2] : Recent fault trip
r0947[3] : Recent fault trip
r0947[4] : Recent fault trip
r0947[5] : Recent fault trip
r0947[6] : Recent fault trip
r0947[7] : Recent fault trip
Example:
If the inverter trips on undervoltage and then receives an external trip before the undervoltage is acknowledged, you will obtain:
-r0947[0] = 3 Undervoltage (F0003)
-r0947[1] = 85 External trip (F0085)
Whenever a fault in index 0 is acknowledged (F1e), the fault history shifts as indicated in the diagram above.
Dependency:
Index 1 used only if second fault occurs before first fault is acknowledged.
Details:
See "Faults and Warnings"
106 | MICROMASTER 440 Parameter List |