Parameter Description

3.12Analog outputs

r0770

Number of DACs

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: TERMINAL

 

Max:

-

Level

3

Displays number of analog outputs available.

P0771[2]

CI: DAC

 

 

 

Min:

0:0

 

CStat:

CUT

Datatype: U32

Unit: -

Def:

21:0

 

P-Group:

TERMINAL

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines function of the 0 - 20 mA analog output.

Index:

P0771[0] : Analog output 1 (DAC 1)

P0771[1] : Analog output 2 (DAC 2)

Common Settings:

21 CO: Act. frequency (scaled to P2000)

24 CO: Act. output frequency (scaled to P2000)

25CO: Act. output voltage (scaled to P2001)

26CO: Act. filtered DC-link volt. (scaled to P2001)

27CO: Act. output current (scaled to P2002)

Level

2

DAC channel

 

 

 

 

P0773

 

 

 

 

 

Function

 

r0xxx P0771

 

 

xxx

 

 

 

 

P0771 = xxx

 

 

 

P0777

P0778

P0779

P0780

DAC scaling

r0774

P0781

DAC

D

dead

A

zone

P0773[2] Smooth time DAC

 

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: ms

Def:

2

P-Group:

TERMINAL

Active: first confirm

QuickComm.: No

Max:

1000

Level

2

Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC using a PT1 filter.

Index:

P0773[0] : Analog output 1 (DAC 1)

P0773[1] : Analog output 2 (DAC 2)

Dependency:

P0773 = 0: Deactivates filter.

r0774[2]

Act. DAC value [mA]

 

Min:

-

 

Datatype: Float

Unit: -

Def:

-

 

P-Group: TERMINAL

 

Max:

-

Level

2

Shows value of analog output in [mA] after filtering and scaling.

Index:

r0774[0] : Analog output 1 (DAC 1)

r0774[1] : Analog output 2 (DAC 2)

P0775[2]

Permit absolute value

 

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

TERMINAL

Active: first confirm

QuickComm.: No

Max:

1

Level

2

Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute value of the value to be outputed. If the value was originally negative then the corresponding bit in R0783 is set, otherwise it is cleared.

Possible Settings:

0OFF

1ON

Index:

P0775[0] : Analog output 1 (DAC 1)

P0775[1] : Analog output 2 (DAC 2)