Issue 01/06

Parameter Description

P2227[3] Fixed PID setpoint mode - Bit 5

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

2

Level

3

Direct selection / direct selection + ON Bit 5 for PID setpoint.

Possible Settings:

1 Direct selection

2 Direct selection + ON command

Index:

P2227[0] :

1st. Command data set (CDS)

P2227[1]

:

2nd. Command data set (CDS)

P2227[2]

:

3rd. Command data set (CDS)

P2228[3] BI: Fixed PID setp. select Bit 5

 

Min:

0:0

Level

 

CStat:

CT

Datatype: U32

Unit: -

Def:

722:5

3

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

 

Defines command source of fixed PID setpoint selection Bit 5

Index:

P2228[0] : 1st. Command data set (CDS)

P2228[1] : 2nd. Command data set (CDS)

P2228[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

P2231[3] Setpoint memory of PID-MOP

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

P-Group:

TECH

Active: Immediately

QuickComm.: No

Max:

1

Setpoint memory

Possible Settings:

0PID-MOP setpoint will not be stored

1PID-MOP setpoint will be stored (P2240 is updated)

Index:

P2231[0] : 1st. Drive data set (DDS)

P2231[1] : 2nd. Drive data set (DDS)

P2231[2] : 3rd. Drive data set (DDS)

Dependency:

If 0 selected, setpoint returns to value set in P2240 (setpoint of PID-MOP) after an OFF command.

If 1 is selected, active setpoint is "remembered" and P2240 updated with current value.

Details:

See P2240 (setpoint of PID-MOP)

Level

2

P2232

Inhibit neg. PID-MOP setpoints

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

1

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

1

Level

2

This parameter suppresses negative setpoints of the PID-MOP output r2250.

Possible Settings:

0Neg. PID-MOP setpoint is allowed

1Neg. PID-MOP setpoint inhibited

Note:

Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase/decrease frequency either by using digital inputs or motor potentiometer up/down buttons.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

229