Siemens 440 manual P22223 BI Fixed PID setp. select Bit, P22233 BI Fixed PID setp. select Bit

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 228
Image 228

Parameter Description

Issue 01/06

P2222[3] BI: Fixed PID setp. select Bit 2

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines command source of fixed PID setpoint selection Bit 2

Index:

P2222[0] : 1st. Command data set (CDS)

P2222[1] : 2nd. Command data set (CDS)

P2222[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

Level

3

P2223[3] BI: Fixed PID setp. select Bit 3

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

722:3

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines command source of fixed PID setpoint selection Bit 3

Index:

P2223[0] : 1st. Command data set (CDS)

P2223[1] : 2nd. Command data set (CDS)

P2223[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

Level

3

r2224

CO: Act. fixed PID setpoint

 

Min:

-

Level

 

Datatype: Float

Unit: %

Def:

-

2

 

 

 

P-Group: TECH

 

Max:

-

 

Displays total output of PID fixed setpoint selection.

Note:

r2224 = 100 % corresponds to 4000 hex

P2225[3] Fixed PID setpoint mode - Bit 4

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

2

Direct selection or direct selection + ON Bit 4 for PID setpoint.

Possible Settings:

1Direct selection

2Direct selection + ON command

Index:

Level

3

P2225[0] : 1st. Command data set (CDS)

P2225[1] : 2nd. Command data set (CDS)

P2225[2] : 3rd. Command data set (CDS)

P2226[3] BI: Fixed PID setp. select Bit 4

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

722:4

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines command source of fixed PID setpoint selection Bit 4

Index:

P2226[0] : 1st. Command data set (CDS)

P2226[1] : 2nd. Command data set (CDS)

P2226[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

Level

3

228

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 228
Image 228
Siemens 440 P22223 BI Fixed PID setp. select Bit, P22233 BI Fixed PID setp. select Bit, R2224 CO Act. fixed PID setpoint