Parameter Description | Issue 01/06 |
It is recommended to modify P0205 first. Afterwards motor parameter may be adapted. Motor parameter will be overridden by changing this sequence.
User
Inverter parameters
r0207 I I,n
r0208 P I,n
r0209 I I,max
P0205 Motor parameters
P0305 I M,n
P0307 P M,n
P0640 I M,max Technology parameter
P0500
P0500
Control parameter
P1300
P1300
Notice:
-The parameter value is not reset by the factory setting (see P0970).
-To set P0205 = 1 (variable torque) is not possible for all inverters.
-Use setting 1 (variable torque) only for
r0206 | Rated inverter power [kW] / [hp] |
| Min: | - |
| Datatype: Float | Unit: - | Def: | - |
|
| Max: | - |
Level
2
Displays nominal rated motor power from inverter.
Dependency:
Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
r0206[hp] = 0.75 ⋅ r0206[kW]
r0207[3] | Rated inverter current |
| Min: | - | Level |
| Datatype: Float | Unit: A | Def: | - | 2 |
|
| ||||
|
|
| Max: | - |
|
Indicates the rated inverter current.
Index:
r0207[0] : Rated inverter current
r0207[1] : Rated VT current
r0207[2] : Rated CT current
Note:
VT (variable torque) and CT (constant torque) specify the overload capability (CT/VT application) of the inverter. The definition of the rated as well as the overload and base load values depend on the inverter type and inverter power. The different values can be taken from the appropriate Catalog or are saved in the drive inverter (refer to Fig.).
The VT rated current r0207[1] or CT rated current r0207[2] represent the matching
Overload in operation is only possible if, before the overload condition, the load current was less than the rated current. For drives, which must be able to handle overload conditions, it is first necessary to define a base load current for the required load.
If the full overload capability is used, then this is detected using an I²t monitoring and the power module is protected as a function of parameter P0290.
r0208 | Rated inverter voltage |
| Min: | - |
| Datatype: U32 | Unit: V | Def: | - |
|
| Max: | - |
Displays nominal AC supply voltage of inverter.
Value:
r0208 = 230 : 200 - 240 V +/- 10 %
r0208 = 400 : 380 - 480 V +/- 10 %
r0208 = 575 : 500 - 600 V +/- 10 %
Level
2
46 | MICROMASTER 440 Parameter List |