Issue 01/06

Parameter Description

P1825

On-state voltage of IGBT

 

Min:

0.0

 

CStat:

CUT

Datatype: Float

Unit: V

Def:

1.4

 

P-Group:

INVERTER

Active: Immediately

QuickComm.: No

Max:

20.0

Corrects on-state voltage of the IGBTs.

Level

4

P1828

Gating unit dead time

 

 

Min:

0.00

 

CStat:

CUT

Datatype: Float

Unit: us

Def:

0.50

 

P-Group:

INVERTER

Active: first confirm

QuickComm.: No

Max:

3.50

Sets compensation time of gating unit interlock.

Level

4

3.31Motor data identification

P1909[3] Ctrl. word of motor data ident.

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: -

Def:

1

P-Group:

CONTROL

Active: first confirm

QuickComm.: No

Max:

1

Control word of motor data identification.

Bitfields:

Level

4

Bit00

Estimation of Xs

0 NO

1 YES

Index:

 

 

 

P1909[0]

: 1st. Drive data set (DDS)

 

 

P1909[1]

: 2nd. Drive data set (DDS)

 

 

P1909[2]

: 3rd. Drive data set (DDS)

 

 

P1910

Select motor data identification

 

Min:

0

Level

 

CStat:

CT

Datatype: U16

Unit: -

Def:

0

2

 

 

 

P-Group:

MOTOR

Active: first confirm

QuickComm.: Yes

Max:

20

 

Performs a motor data identification.

Possible Settings:

0Disabled

1Identification of all parameters with parameter change

2Identification of all parameters without parameter change

3Identification of saturation curve with parameter change

4Identification of saturation curve without parameter change

5Identification of XsigDyn (r1920) without parameter change

6Identification of Tdead (r1926) without parameter change

7Identification of Rs (r1912 ) without parameter change

8Identification of Xs (r1915) without parameter change

9Identification of Tr (r1913) without parameter change

10Identification of Xsigma (r1914) without parameter change

20Set voltage vector

Common Settings:

P1910 = 1:

All motor data and inverter characteristic will be identified and parameter will be changed.

-P0350 stator resistance,

-P0354 rotor resistance,

-P0356 stator leakage inductance,

-P0358 rotor leakage inductance,

-P0360 main inductance

-P1825 on-state voltage of IGBTs

-P1828 compensation time of gating unit interlock

P1910 = 3:

Saturation curve will be identified and parameter will be changed.

-P0362 ... P0365 magnetizing curve flux 1 .. 4

-P0366 ... P0369 magnetizing curve imag 1 .. 4

Caution:

Motor identification should normally be performed on a cold motor. However, the identification of the motor data should only be performed if the motor temperature is within 5°C of the measured ambient temperature stored in P0625. If the motor identification is not within the 5ºC limit then the correct functioning of Vector Control (VC, SLVC) cannot be guaranteed. This may cause instabilities when using vector control.

The motor rating plate information with respect to the connection of the motor windings (Star or delta connection) must be correct in order to establish the correct equivalent circuit data. The motor identification calculates this data based on a Phase of a Star equivalent circuit P0350 - P0360, irrespective of whether the motor is connected star or delta. This must be considered when the motor data is input directly.

Note:

-In order to that the motor identification routine supplies the correct data, before selecting, fast commissioning should be carried-out.

-If the motor data identification routine is activated (e.g. P1910 = 1), then at the next ON command, the measuring operation is started and alarm A0541 is generated. After the measurement is completed, both P1910 and the alarm are reset.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

189