Parameter Description

Issue 01/06

P2184[3] Belt threshold frequency 3

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

50.00

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

650.00

Level

2

Sets a threshold F3 for comparing actual torque to torque the envelope for belt failure detection.

Index:

P2184[0] : 1st. Drive data set (DDS)

P2184[1] : 2nd. Drive data set (DDS)

P2184[2] : 3rd. Drive data set (DDS)

Details:

See P2182 (belt threshold frequency 1).

P2185[3] Upper torque threshold 1

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: Nm

Def:

99999.0

2

 

 

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

99999.0

 

Upper limit threshold value 1 for comparing actual torque.

Index:

P2185[0] : 1st. Drive data set (DDS)

P2185[1] : 2nd. Drive data set (DDS)

P2185[2] : 3rd. Drive data set (DDS)

Details:

See P2182 (belt threshold frequency 1).

P2186[3] Lower torque threshold 1

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: Nm

Def:

0.0

2

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

99999.0

 

Lower limit threshold value 1 for comparing actual torque.

Index:

P2186[0] : 1st. Drive data set (DDS)

P2186[1] : 2nd. Drive data set (DDS)

P2186[2] : 3rd. Drive data set (DDS)

Details:

See P2182 (belt threshold frequency 1).

P2187[3] Upper torque threshold 2

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: Nm

Def:

99999.0

2

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

99999.0

 

Upper limit threshold value 2 for comparing actual torque.

Index:

P2187[0] : 1st. Drive data set (DDS)

P2187[1] : 2nd. Drive data set (DDS)

P2187[2] : 3rd. Drive data set (DDS)

Details:

See P2182 (belt threshold frequency 1).

P2188[3] Lower torque threshold 2

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: Nm

Def:

0.0

2

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

99999.0

 

Lower limit threshold value 2 for comparing actual torque.

Index:

P2188[0] : 1st. Drive data set (DDS)

P2188[1] : 2nd. Drive data set (DDS)

P2188[2] : 3rd. Drive data set (DDS)

Details:

See P2182 (belt threshold frequency 1).

P2189[3] Upper torque threshold 3

 

Min:

0.0

Level

 

CStat:

CUT

Datatype: Float

Unit: Nm

Def:

99999.0

2

 

 

 

P-Group:

ALARMS

Active: Immediately

QuickComm.: No

Max:

99999.0

 

Upper limit threshold value 3 for comparing actual torque.

Index:

P2189[0] : 1st. Drive data set (DDS)

P2189[1] : 2nd. Drive data set (DDS)

P2189[2] : 3rd. Drive data set (DDS)

Details:

See P2182 (belt threshold frequency 1).

220