Parameter Description

r0968

Status word 1

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: COMM

 

Max:

-

Level

3

Displays active status word of inverter (in binary) and can be used to diagnose which commands are active.

Bitfields:

 

 

 

 

 

 

 

 

Bit00

Drive ready

 

0

NO

1

YES

 

Bit01

Drive ready to run

0

NO

1

YES

 

Bit02

Drive running

 

0

NO

1

YES

 

Bit03

Drive fault active

0

NO

1

YES

 

Bit04

OFF2 active

 

0

YES

1

NO

 

Bit05

OFF3 active

 

0

YES

1

NO

 

Bit06

ON inhibit active

0

NO

1

YES

 

Bit07

Drive warning active

0

NO

1

YES

 

Bit08

Deviation setpoint / act. value

0

YES

1

NO

 

Bit09

PZD control

 

0

NO

1

YES

 

Bit10

Maximum frequency reached

0

NO

1

YES

 

Bit11

Warning: Motor current limit

0

YES

1

NO

 

Bit12

Motor holding brake active

0

NO

1

YES

 

Bit13

Motor overload

 

0

YES

1

NO

 

Bit14

Motor runs right

0

NO

1

YES

 

Bit15

Inverter overload

0

YES

1

NO

P0970

Factory reset

 

 

Min:

0

 

Level

 

CStat:

C

Datatype: U16

Unit: -

Def:

0

 

1

 

P-Group:

PAR_RESET

Active: first confirm

QuickComm.: No Max:

1

 

 

P0970 = 1 resets all parameters to their default values.

Possible Settings:

0Disabled

1Parameter reset

Dependency:

- First set P0010 = 30 (factory settings).

- Stop drive (i.e. disable all pulses) before you can reset parameters to default values.

Note:

The following parameters retain their values after a factory reset:

-

P0014

Store mode

-

r0039 CO: Energy consumption meter [kWh]

-

P0100

Europe / North America

-

P0918

CB address

-

P2010

USS baud rate

-

P2011

USS address

P0971

Transfer data from RAM to EEPROM

 

Min:

0

Level

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

3

 

 

 

P-Group:

COMM

Active: first confirm

QuickComm.: No

Max:

1

 

Transfers values from RAM to EEPROM when set to 1.

Possible Settings:

0Disabled

1Start transfer

Note:

All values in RAM are transferred to EEPROM.

Parameter is automatically reset to 0 (default) after successful transfer.

The storage from RAM to EEPROM is accomplished via P0971. The communications are reset, if the transfer was successful. During the reset process communications will be interrupted. This creates the following conditions:

-PLC (e.g. SIMATIC S7) enters Stop mode

-Starter automatically recovers communications once they are re-established.

-Drivemonitor is displayed "NC" (not connected) in the status line or "drive busy".

-BOP displays "busy"

After completion of the transfer process, the communication between the inverter and the PC-tools (e.g. Starter) or BOP is automatically re-established.

MICROMASTER 440