Issue 01/06 | Parameter Description |
r0968 | Status word 1 |
| Min: | - |
| Datatype: U16 | Unit: - | Def: | - |
|
| Max: | - |
Level
3
Displays active status word of inverter (in binary) and can be used to diagnose which commands are active.
Bitfields: |
|
|
|
|
|
|
| |
| Bit00 | Drive ready |
| 0 | NO | 1 | YES | |
| Bit01 | Drive ready to run | 0 | NO | 1 | YES | ||
| Bit02 | Drive running |
| 0 | NO | 1 | YES | |
| Bit03 | Drive fault active | 0 | NO | 1 | YES | ||
| Bit04 | OFF2 active |
| 0 | YES | 1 | NO | |
| Bit05 | OFF3 active |
| 0 | YES | 1 | NO | |
| Bit06 | ON inhibit active | 0 | NO | 1 | YES | ||
| Bit07 | Drive warning active | 0 | NO | 1 | YES | ||
| Bit08 | Deviation setpoint / act. value | 0 | YES | 1 | NO | ||
| Bit09 | PZD control |
| 0 | NO | 1 | YES | |
| Bit10 | Maximum frequency reached | 0 | NO | 1 | YES | ||
| Bit11 | Warning: Motor current limit | 0 | YES | 1 | NO | ||
| Bit12 | Motor holding brake active | 0 | NO | 1 | YES | ||
| Bit13 | Motor overload |
| 0 | YES | 1 | NO | |
| Bit14 | Motor runs right | 0 | NO | 1 | YES | ||
| Bit15 | Inverter overload | 0 | YES | 1 | NO | ||
P0970 | Factory reset |
|
| Min: | 0 |
| Level | |
| CStat: | C | Datatype: U16 | Unit: - | Def: | 0 |
| 1 |
| PAR_RESET | Active: first confirm | QuickComm.: No Max: | 1 |
|
|
P0970 = 1 resets all parameters to their default values.
Possible Settings:
0Disabled
1Parameter reset
Dependency:
- First set P0010 = 30 (factory settings).
- Stop drive (i.e. disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset:
- | P0014 | Store mode |
- | r0039 CO: Energy consumption meter [kWh] | |
- | P0100 | Europe / North America |
- | P0918 | CB address |
- | P2010 | USS baud rate |
- | P2011 | USS address |
P0971 | Transfer data from RAM to EEPROM |
| Min: | 0 | Level | ||
| CStat: | CUT | Datatype: U16 | Unit: - | Def: | 0 | 3 |
|
| ||||||
| COMM | Active: first confirm | QuickComm.: No | Max: | 1 |
|
Transfers values from RAM to EEPROM when set to 1.
Possible Settings:
0Disabled
1Start transfer
Note:
All values in RAM are transferred to EEPROM.
Parameter is automatically reset to 0 (default) after successful transfer.
The storage from RAM to EEPROM is accomplished via P0971. The communications are reset, if the transfer was successful. During the reset process communications will be interrupted. This creates the following conditions:
-PLC (e.g. SIMATIC S7) enters Stop mode
-Starter automatically recovers communications once they are
-Drivemonitor is displayed "NC" (not connected) in the status line or "drive busy".
-BOP displays "busy"
After completion of the transfer process, the communication between the inverter and the
MICROMASTER 440 | Parameter List |
109 |