Parameter Description

Issue 01/06

r0075

CO: Current setpoint Isd

 

Min:

-

 

Datatype: Float

Unit: A

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

3

Displays setpoint of flux generating current component.

Dependency:

Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.

r0076

CO: Act. current Isd

 

Min:

-

 

Datatype: Float

Unit: A

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

3

Displays flux generating current component.

Dependency:

Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.

r0077

CO: Current setpoint Isq

 

Min:

-

 

Datatype: Float

Unit: A

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

3

Displays setpoint for component of torque generating current.

Dependency:

Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.

r0078

CO: Act. current Isq

 

Min:

-

 

Datatype: Float

Unit: A

Def:

-

 

P-Group: CONTROL

 

Max:

-

Displays component of torque generating current.

Level

3

r0079

CO: Torque setpoint (total)

 

Min:

-

 

Datatype: Float

Unit: Nm

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

3

Displays total torque setpoint.

Dependency:

Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.

r0080

CO: Act. torque

 

Min:

-

 

Datatype: Float

Unit: Nm

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

4

Displays actual torque. Output value will be zero at low frequencies when current injection is active (r1751.5 = 1).

r0084

CO: Act. air gap flux

 

Min:

-

 

Datatype: Float

Unit: %

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

4

Displays air gap flux in [%] relative to the rated motor flux.

r0086

CO: Act. active current

 

Min:

-

 

Datatype: Float

Unit: A

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

3

Displays active (real part) of motor current.

Dependency:

Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.

r0090

CO: Act. rotor angle

 

Min:

-

 

Datatype: Float

Unit: °

Def:

-

 

P-Group: CONTROL

 

Max:

-

Level

2

Indicates the current angle of the rotor. This function is not available on single input channel encoders.

40

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 40
Image 40