Issue 01/06

Parameter Description

P0708[3] Function of digital input 8

 

Min:

0

CStat:

CT

Datatype: U16

Unit: -

Def:

0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

99

Level

2

Selects function of digital input 8 (via analog input)

Possible Settings:

0Digital input disabled

1ON/OFF1

2ON reverse /OFF1

3

OFF2 - coast to standstill

4OFF3 - quick ramp-down

9Fault acknowledge

10JOG right

11JOG left

12Reverse

13MOP up (increase frequency)

14MOP down (decrease frequency)

25DC brake enable

29External trip

33Disable additional freq setpoint

99Enable BICO parameterization

Index:

P0708[0] : 1st. Command data set (CDS)

P0708[1] : 2nd. Command data set (CDS)

P0708[2] : 3rd. Command data set (CDS)

Note:

Signals above 4 V are active, signals below 1,6 V are inactive.

Details:

See P0701 (function of digital input 1).

P0719[3] Selection of cmd. & freq. setp.

 

Min:

0

CStat:

CT

Datatype: U16

Unit: -

Def:

0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

67

Level

3

Central switch to select control command source for inverter.

Switches command and setpoint source between freely programmable BICO parameters and fixed command/setpoint profiles. Command and setpoint sources can be changed independently.

The tens digit chooses the command source and the units digit chooses the setpoint source.

Possible Settings:

 

0

Cmd = BICO parameter

Setpoint = BICO parameter

1

Cmd = BICO parameter

Setpoint = MOP setpoint

2

Cmd = BICO parameter

Setpoint = Analog setpoint

3

Cmd = BICO parameter

Setpoint = Fixed frequency

4

Cmd = BICO parameter

Setpoint = USS on BOP link

5

Cmd = BICO parameter

Setpoint = USS on COM link

6

Cmd = BICO parameter

Setpoint = CB on COM link

7

Cmd = BICO parameter

Setpoint = Analog 2 setp

10

Cmd = BOP

Setpoint = BICO parameter

11

Cmd = BOP

Setpoint = MOP setpoint

12

Cmd = BOP

Setpoint = Analog setpoint

13

Cmd = BOP

Setpoint = Fixed frequency

15

Cmd = BOP

Setpoint = USS on COM link

16

Cmd = BOP

Setpoint = CB on COM link

17

Cmd = BOP

Setpoint = Analog 2 setp

40

Cmd = USS on BOP link

Setpoint = BICO parameter

41

Cmd = USS on BOP link

Setpoint = MOP setpoint

42

Cmd = USS on BOP link

Setpoint = Analog setpoint

43

Cmd = USS on BOP link

Setpoint = Fixed frequency

44

Cmd = USS on BOP link

Setpoint = USS on BOP link

45

Cmd = USS on BOP link

Setpoint = USS on COM link

46

Cmd = USS on BOP link

Setpoint = CB on COM link

47

Cmd = USS on BOP link

Setpoint = Analog 2 setp

50

Cmd = USS on COM link

Setpoint = BICO parameter

51

Cmd = USS on COM link

Setpoint = MOP setpoint

52

Cmd = USS on COM link

Setpoint = Analog setpoint

53

Cmd = USS on COM link

Setpoint = Fixed frequency

54

Cmd = USS on COM link

Setpoint = USS on BOP link

55

Cmd = USS on COM link

Setpoint = USS on COM link

57

Cmd = USS on COM link

Setpoint = Analog 2 setp

60

Cmd = CB on COM link

Setpoint = BICO parameter

61

Cmd = CB on COM link

Setpoint = MOP setpoint

62

Cmd = CB on COM link

Setpoint = Analog setpoint

63

Cmd = CB on COM link

Setpoint = Fixed frequency

64

Cmd = CB on COM link

Setpoint = USS on BOP link

66

Cmd = CB on COM link

Setpoint = CB on COM link

67

Cmd = CB on COM link

Setpoint = Analog 2 setp

MICROMASTER 440

Parameter List

81

6SE6400-5BB00-0BP0

Page 81
Image 81
Siemens 440 manual P07083 Function of digital input, P07193 Selection of cmd. & freq. setp