Issue 01/06

Parameter Description

3.40Inverter parameters

P3900

End of quick commissioning

 

Min:

0

 

CStat:

C

Datatype: U16

Unit: -

Def:

0

 

P-Group:

QUICK

Active: first confirm

QuickComm.: Yes

Max:

3

Performs calculations necessary for optimized motor operation.

Level

1

After completion of calculation, P3900 and P0010 (parameter groups for commissioning) are automatically reset to their original value 0.

Possible Settings:

0No quick commissioning

1Start quick commissioning with factory reset

2Start quick commissioning

3Start quick commissioning only for motor data

Dependency:

Changeable only when P0010 = 1 (quick commissioning)

Note:

P3900 = 1 :

When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning", are retained; all other parameter changes, including the I/O settings, are lost. Motor calculations are also performed.

P3900 = 2 :

When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the motor calculations performed.

P3900 = 3 :

When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with this setting saves time (for example, if only motor rating plate data have been changed).

Calculates a variety of motor parameters, overwriting previous values (see parameter P0340, setting P0340 = 1).

P3950

Access of hidden parameters

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

ALWAYS

Active: first confirm

QuickComm.: No

Max:

255

Level

4

Accesses special parameters for development (expert only) and factory functionality (calibration parameter).

r3954[13] CM version and GUI ID

 

Min:

-

Datatype: U16

Unit: -

Def:

-

P-Group: -

 

Max:

-

Used to classify firmware (only for SIEMENS internal purposes).

Index:

r3954[0] : CM version (major release)

r3954[1] : CM version (minor release)

r3954[2] : CM version (baselevel or patch)

r3954[3] : GUI ID

r3954[4] : GUI ID

r3954[5] : GUI ID

r3954[6] : GUI ID

r3954[7] : GUI ID

r3954[8] : GUI ID

r3954[9] : GUI ID

r3954[10] : GUI ID

r3954[11] : GUI ID major release

r3954[12] : GUI ID minor release

Level

4

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

257

Page 257
Image 257