Issue 01/06

Parameter Description

P2218[3] Fixed PID setpoint mode - Bit 2

 

Min:

1

CStat:

CT

Datatype: U16

Unit: -

Def:

1

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

3

BCD or direct selection Bit 2 for PID setpoint.

Possible Settings:

1Direct selection

2Direct selection + ON command

3Binary coded selection + ON command

Index:

Level

3

P2218[0] :

1st. Command data set (CDS)

P2218[1]

:

2nd. Command data set (CDS)

P2218[2]

:

3rd. Command data set (CDS)

P2219[3] Fixed PID setpoint mode - Bit 3

 

Min:

1

Level

 

CStat:

CT

Datatype: U16

Unit: -

Def:

1

3

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

3

 

 

 

BCD or direct selection Bit 3 for PID setpoint.

 

 

 

 

Possible Settings:

 

 

 

 

 

 

 

1 Direct selection

 

 

 

 

 

 

2 Direct selection + ON command

 

 

 

 

 

3 Binary coded selection + ON command

 

 

 

 

Index:

 

 

 

 

 

 

 

P2219[0] : 1st. Command data set (CDS)

 

 

 

 

 

P2219[1] : 2nd. Command data set (CDS)

 

 

 

 

 

P2219[2] : 3rd. Command data set (CDS)

 

 

 

 

P2220[3] BI: Fixed PID setp. select Bit 0

 

Min:

0:0

Level

 

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

3

 

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

 

Defines command source of fixed PID setpoint selection Bit 0

Index:

P2220[0] : 1st. Command data set (CDS)

P2220[1] : 2nd. Command data set (CDS)

P2220[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

P2221[3] BI: Fixed PID setp. select Bit 1

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines command source of fixed PID setpoint selection Bit 1.

Index:

P2221[0] : 1st. Command data set (CDS)

P2221[1] : 2nd. Command data set (CDS)

P2221[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

Level

3

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

227

Page 227
Image 227
Siemens 440 P22183 Fixed PID setpoint mode Bit, P22193 Fixed PID setpoint mode Bit, P22203 BI Fixed PID setp. select Bit