Parameter Description

Issue 01/06

P1060[3] JOG ramp-up time

 

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: s

Def:

10.00

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

650.00

Sets jog ramp-up time. This is the time used while jogging is active.

JOG

Level

2

f (Hz)

 

 

 

f max

 

 

 

(P1082)

 

 

 

P1058

 

 

 

0

t (s)

 

 

tup

P1058

 

P1060

tup =

P1060

 

P1082

 

Index:

P1060[0] : 1st. Drive data set (DDS)

P1060[1] : 2nd. Drive data set (DDS)

P1060[2] : 3rd. Drive data set (DDS)

Notice:

Ramp times will be used as follows:

-P1060 / P1061 : JOG mode is active

-P1120 / P1121 : Normal mode (ON/OFF) is active

-P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active

P1061[3] JOG ramp-down time

 

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: s

Def:

10.00

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

650.00

Level

2

Sets ramp-down time. This is the time used while jogging is active.

JOG

f (Hz)

f max

 

(P1082)

 

P1058

 

0

t (s)

tdown

P1061

 

Index:

= P1058

tdown P1082 P1061

P1061[0] : 1st. Drive data set (DDS)

P1061[1] : 2nd. Drive data set (DDS)

P1061[2] : 3rd. Drive data set (DDS)

Notice:

Ramp times will be used as follows:

-P1060 / P1061 : JOG mode is active

-P1120 / P1121 : Normal mode (ON/OFF) is active

-P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active