Parameter Description

Issue 01/06

3.19JOG

P1055[3] BI: Enable JOG right

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source of JOG right.

Index:

P1055[0] : 1st. Command data set (CDS)

P1055[1] : 2nd. Command data set (CDS)

P1055[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.8= JOG right via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Level

3

P1056[3] BI: Enable JOG left

 

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source of JOG left.

Index:

P1056[0] : 1st. Command data set (CDS)

P1056[1] : 2nd. Command data set (CDS)

P1056[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.9= JOG left via BOP

Dependency:

Active only when P0719 < 10. See parameter P0719 (Selection of command/setpoint source).

Level

3

122

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 122
Image 122
Siemens 440 manual 19 JOG, P10553 BI Enable JOG right, P10563 BI Enable JOG left