MICROMASTER 440 6SE6400-

Seven-segment display

Segment Bit 15 14 13 12 11 10 9 8

Segment Bit 7 6

5 4

3 2

1 0

 

 

 

 

 

Parameter r0053

 

 

 

 

 

 

 

 

 

Bit No.

 

Meaning

 

 

 

 

 

 

Braking control

 

 

0

1

= DC brake active

 

 

0

= DC brake not active

 

 

 

 

 

Alarm processing

 

 

 

 

 

 

 

1

1

= f_act > P2167 (f_off)

 

 

 

 

 

 

 

Messages

 

 

2

1

= f_act >= P1080 (f_min)

 

 

 

 

 

 

 

Alarm processing

 

 

3

1

= Act. current r0027 >= P2170

 

 

 

 

 

 

 

Messages

 

 

4

1

= f_act > P2155 (f_1)

 

 

 

 

 

 

 

Messages

 

 

5

1

= f_act <= P2155 (f_1)

 

 

 

 

 

 

 

Messages

 

 

6

1

= f_act >= setpoint

 

 

 

 

 

 

 

Messages

 

 

7

1

= Act. Vdc r0026 < P2172

 

 

 

 

 

 

 

Alarm processing

 

 

8

1

= Act. Vdc r0026 > P2172

 

 

 

 

 

 

 

Sequence control 1)

 

 

9

1

= Ramping finished

 

 

 

 

 

 

 

Messages

 

 

10

1

= PID output r2294 == P2292 (PID_min)

 

 

 

 

 

 

 

Messages

 

 

11

1

= PID output r2294 == P2291 (PID_max)

 

 

 

 

 

 

 

 

12

reserved

 

 

 

 

 

 

 

13

reserved

 

 

 

 

 

Sequence control 1)

 

 

14

Download data set 0 from AOP

 

Sequence control 1)

 

 

 

 

 

 

15

Download data set 1 from AOP

 

 

 

 

 

 

 

CO/BO: Act StatWd2

r0053

r0053

1)The sequence control is the internal control (software) for realizing the drive status (r0002)

Function Diagrams

Parameter List 5BB00-0BP0

1

 

2

3

4

5

6

7

 

8

Technology Functions

 

 

 

 

4180_ZSW2.vsd

Function diagram

 

- 4180 -

Status word 2 (r0053)

 

 

 

 

16.01.2006 V2.1