Siemens 440 manual R03133 Motor pole pairs, P03143 Motor pole pair number, R03303 Rated motor slip

Models: 440

1 328
Download 328 pages 28.01 Kb
Page 54
Image 54

Parameter Description

Issue 01/06

r0313[3]

Motor pole pairs

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: MOTOR

 

Max:

-

Displays number of motor pole pairs that the inverter is currently using for internal calculations.

Index:

r0313[0] : 1st. Drive data set (DDS)

r0313[1] : 2nd. Drive data set (DDS)

r0313[2] : 3rd. Drive data set (DDS)

Value:

Level

3

r0313 = 1 : 2-pole motor

r0313 = 2 : 4-pole motor etc.

Dependency:

Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed.

r0313 = 60 P0310P0311

P0314[3] Motor pole pair number

 

 

Min:

0

Level

 

CStat:

C

Datatype: U16

Unit: -

Def:

0

3

 

 

 

P-Group:

MOTOR

Active: first confirm

QuickComm.: Yes

Max:

99

 

Specifies number of pole pairs of motor.

Index:

P0314[0] : 1st. Drive data set (DDS)

P0314[1] : 2nd. Drive data set (DDS)

P0314[2] : 3rd. Drive data set (DDS)

Value:

P0314 = 1 : 2-pole motor

P0314 = 2 : 4-pole motor etc.

Dependency:

Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed) is changed.

P0320[3] Motor magnetizing current

 

Min:

0.0

CStat:

CT

Datatype: Float

Unit: %

Def:

0.0

P-Group:

MOTOR

Active: Immediately

QuickComm.: Yes

Max:

99.0

Level

3

Defines motor magnetization current in [%] relative to P0305 (rated motor current).

Index:

P0320[0] : 1st. Drive data set (DDS)

P0320[1] : 2nd. Drive data set (DDS)

P0320[2] : 3rd. Drive data set (DDS)

Dependency:

Setting P0320 = 0: causes calculation by

-P0340 = 1 (data entered from rating plate) or by

-P3900 = 1 - 3 (end of quick commissioning). The calculated value is displayed in parameter r0331.

r0330[3]

Rated motor slip

 

Min:

-

 

Datatype: Float

Unit: %

Def:

-

 

P-Group: MOTOR

 

Max:

-

Level

3

Displays nominal motor slip in [%] relative to P0310 (rated motor frequency) and P0311 (rated motor speed).

 

 

 

P0310

P0311r0313

 

 

 

 

 

r0330[%] =

 

60

 

100%

 

 

 

 

 

 

P0310

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Index:

r0330[0]

: 1st. Drive data set (DDS)

 

 

 

 

 

 

 

 

 

 

r0330[1]

: 2nd. Drive data set (DDS)

 

 

 

 

 

r0330[2]

: 3rd. Drive data set (DDS)

 

 

 

 

r0331[3]

Rated magnetization current

 

Min:

-

Level

 

 

 

 

 

Datatype: Float

Unit: A

Def:

-

3

 

P-Group: MOTOR

 

 

 

 

Max:

-

 

Displays calculated magnetizing current of motor in [A].

Index:

r0331[0] : 1st. Drive data set (DDS)

r0331[1] : 2nd. Drive data set (DDS)

r0331[2] : 3rd. Drive data set (DDS)

54

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 54
Image 54
Siemens 440 manual R03133 Motor pole pairs, P03143 Motor pole pair number, P03203 Motor magnetizing current