Issue 01/06

Parameter Description

r1084

Resultant max. frequency

 

Min:

-

 

 

 

Datatype: Float

Unit: Hz

Def:

-

 

P-Group:

CONTROL

 

 

Max:

-

 

Displays resultant maximum frequency.

 

 

 

 

P1300 < 20

 

 

 

 

 

P1800

6 kHz

r1084 = min(P1082, P1800

, 650.00)

 

 

 

 

 

15

 

 

 

 

P1800

8 kHz

r1084 = min (P1082,650.00)

 

 

 

P1300 20

 

 

 

 

 

r1084=

min(P1082, 5 P0310, 200.00)

 

 

 

Level

3

P1091[3] Skip frequency 1

 

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

0.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Level

3

Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).

fout

P1101

Skip frequency

bandwidth

fin

P1091

Skip frequency

Index:

P1091[0] : 1st. Drive data set (DDS)

P1091[1] : 2nd. Drive data set (DDS)

P1091[2] : 3rd. Drive data set (DDS)

Notice:

-Stationary operation is not possible within the suppressed frequency range; the range is merely passed through (on the ramp).

-For example, if P1091 = 10 Hz and P1101 = 2 Hz, it is not possible to operate continuously between 10 Hz +/- 2 Hz (i.e. between 8 and 12 Hz).

P1092[3] Skip frequency 2

 

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

0.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Level

3

Defines skip frequency 2 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).

Index:

P1092[0] : 1st. Drive data set (DDS)

P1092[1] : 2nd. Drive data set (DDS)

P1092[2] : 3rd. Drive data set (DDS)

Details:

See P1091 (skip frequency 1).

P1093[3] Skip frequency 3

 

 

Min:

0.00

CStat:

CUT

Datatype: Float

Unit: Hz

Def:

0.00

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

650.00

Level

3

Defines skip frequency 3 which avoids effects of mechanical resonance and suppresses frequencies within +/- P1101 (skip frequency bandwidth).

Index:

P1093[0] : 1st. Drive data set (DDS)

P1093[1] : 2nd. Drive data set (DDS)

P1093[2] : 3rd. Drive data set (DDS)

Details:

See P1091 (skip frequency 1).

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

129

Page 129
Image 129
Siemens 440 manual R1084 Resultant max. frequency, P10913 Skip frequency, P10923 Skip frequency, P10933 Skip frequency, 129