Parameter Description

Issue 01/06

P1232[3]

DC braking current

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: %

Def:

100

 

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

250

Level

2

Defines level of DC current in [%] relative to rated motor current (P0305).

r0027DCBrake[A] 1

P0305

P1232

2

 

100%

The current of the DC-braking is limited by r0067.

Index:

P1232[0] : 1st. Drive data set (DDS)

P1232[1] : 2nd. Drive data set (DDS)

P1232[2] : 3rd. Drive data set (DDS)

P1233[3]

Duration of DC braking

 

 

Min:

0.00

Level

 

CStat:

CUT

Datatype: Float

Unit: s

Def:

0.00

2

 

 

 

P-Group:

FUNC

Active: Immediately

QuickComm.: No

Max:

250.00

 

Defines duration for which DC injection braking is to be active following an OFF1 or OFF3 command. When an OFF1 or OFF3 command is received by the drive, the output frequency starts to ramp to 0 Hz. When the output frequency reaches the value set in P1234, the drive injects a DC braking current P1232 for the time duration set in P1233.

1

ON

OFF1/OFF3

OFF2

f

P1234

DC braking active

t

P0347

t

OFF2

DC braking

t

r0053

1

 

Bit00

0

t

 

 

P1233

2

ON

OFF1/OFF3

t

P0347

OFF2

t

f

P1234

OFF ramp

OFF2

 

 

DC braking

 

 

 

 

 

 

OFF2

DC braking active

 

t

 

 

r0053

1

 

 

Bit00

0

 

t

 

 

 

P1233

The DC current, that is impressed during time P1233, is specified by parameter P1232.

144

MICROMASTER 440 Parameter List

6SE6400-5BB00-0BP0

Page 144
Image 144