Issue 01/06

Parameter Description

3.13Parameter / command / drive data set

P0800[3] BI: Download parameter set 0

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines source of command to start download of parameter set 0 from attached AOP.

Index:

P0800[0] : 1st. Command data set (CDS)

P0800[1] : 2nd. Command data set (CDS)

P0800[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

Dependency:

1.The parameter set 0 can only be downloaded in conjunction with the AOP

2.Establish communications between the frequency inverter and AOP

3.The frequency inverter must be selected using the AOP if the AOP is connected at the COM link interface (RS485)

4.Select the frequency inverter state "Ready" (r0002 = 1)

5.Signal from P0800:

0 = Do not download.

1 = Start to download parameter set 0 from the AOP.

Inverter

BI: Dwnl .par.set 0

P0800.C

(0:0)

r0002 = 1

"Drive ready"

&

AOP

BOP link or COM link

Parameter set0

Parameter. set1

.

.

Parameter set9

Transmission of "Parameter set 0" from AOP to inverter

P0801[3] BI: Download parameter set 1

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

0:0

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Defines sources of command to start download of parameter set 1 from attached AOP.

Index:

P0801[0] : 1st. Command data set (CDS)

P0801[1] : 2nd. Command data set (CDS)

P0801[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

Note:

See parameter P0800

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

97

Page 97
Image 97
Siemens 440 manual Parameter / command / drive data set, P08003 BI Download parameter set, P08013 BI Download parameter set