Parameter Description

Issue 01/06

3.18Motorized potentiometer (MOP)

P1031[3] Setpoint memory of the MOP

 

Min:

0

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

P-Group:

SETPOINT

Active: Immediately

QuickComm.: No

Max:

1

Level

2

Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.

Possible Settings:

0MOP setpoint will not be stored

1MOP setpoint will be stored (P1040 is updated)

Index:

P1031[0] : 1st. Drive data set (DDS)

P1031[1] : 2nd. Drive data set (DDS)

P1031[2] : 3rd. Drive data set (DDS)

Note:

On next ON command, motor potentiometer setpoint will be the saved value in parameter P1040 (setpoint of the MOP).

P1032

Inhibit negative MOP setpoints

 

Min:

0

 

CStat:

CT

Datatype: U16

Unit: -

Def:

1

 

P-Group:

SETPOINT

Active: first confirm

QuickComm.: No

Max:

1

Level

2

This parameter suppresses negative setpoints of the MOP output r1050.

Possible Settings:

0Neg. MOP setpoint is allowed

1Neg. MOP setpoint inhibited

Note:

The reversing functions (e.g. BOP-Reverse button if P0700 = 1) are not affected by the settings of P1032. Use P1110 to fully prevent change of direction in setpoint channel.

P1035[3] BI: Enable MOP (UP-command)

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

19:13

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source for motor potentiometer setpoint increase frequency.

Index:

P1035[0] : 1st. Command data set (CDS)

P1035[1] : 2nd. Command data set (CDS)

P1035[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.D = MOP up via BOP

Level

3

P1036[3] BI: Enable MOP (DOWN-command)

 

Min:

0:0

CStat:

CT

Datatype: U32

Unit: -

Def:

19:14

P-Group:

COMMANDS

Active: first confirm

QuickComm.: No

Max:

4000:0

Defines source for motor potentiometer setpoint decrease frequency.

Index:

P1036[0] : 1st. Command data set (CDS)

P1036[1] : 2nd. Command data set (CDS)

P1036[2] : 3rd. Command data set (CDS)

Common Settings:

722.0= Digital input 1 (requires P0701 to be set to 99, BICO)

722.1= Digital input 2 (requires P0702 to be set to 99, BICO)

722.2= Digital input 3 (requires P0703 to be set to 99, BICO)

722.3= Digital input 4 (requires P0704 to be set to 99, BICO)

722.4= Digital input 5 (requires P0705 to be set to 99, BICO)

722.5= Digital input 6 (requires P0706 to be set to 99, BICO)

722.6= Digital input 7 (via analog input 1, requires P0707 to be set to 99)

722.7= Digital input 8 (via analog input 2, requires P0708 to be set to 99)

19.E = MOP down via BOP

Level

3

120