Issue 01/06

Parameter Description

P2851

Mode timer 1

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

13

Level

3

Selects mode of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.

Possible Settings:

0ON delay (seconds)

1OFF delay (seconds)

2ON/OFF delay (seconds)

3Pulse generator (seconds)

10ON delay (minutes)

11OFF delay (minutes)

12ON/OFF delay (minutes)

13Pulse generator (minutes)

Dependency:

P2802[0] is active level for the timer.

r2852

BO: Timer 1

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: TECH

 

Max:

-

Level

3

Displays output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.

Dependency:

P2802[0] is active level for the timer.

r2853

BO: Nout timer 1

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: TECH

 

Max:

-

Level

3

Displays Not-output of timer 1. P2849, P2850, P2851 are the inputs of the timer, outputs are P2852, P2853.

Dependency:

P2802[0] is active level for the timer.

P2854

BI: Timer 2

 

 

Min:

0:0

 

CStat:

CUT

Datatype: U32

Unit: -

Def:

0:0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

4000:0

Level

3

Define input signal of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.

Dependency:

P2802[1] is active level for the timer.

P2855

Delay time of timer 2

 

 

Min:

0.0

 

CStat:

CUT

Datatype: Float

Unit: -

Def:

0.0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

9999.9

Level

3

Defines delay time of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.

Dependency:

P2802[1] is active level for the timer.

P2856

Mode timer 2

 

 

Min:

0

 

CStat:

CUT

Datatype: U16

Unit: -

Def:

0

 

P-Group:

TECH

Active: first confirm

QuickComm.: No

Max:

13

Level

3

Selects mode of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.

Possible Settings:

0ON delay (seconds)

1OFF delay (seconds)

2ON/OFF delay (seconds)

3Pulse generator (seconds)

10ON delay (minutes)

11OFF delay (minutes)

12ON/OFF delay (minutes)

13Pulse generator (minutes)

Dependency:

P2802[1] is active level for the timer.

r2857

BO: Timer 2

 

Min:

-

 

Datatype: U16

Unit: -

Def:

-

 

P-Group: TECH

 

Max:

-

Level

3

Displays output of timer 2. P2854, P2855, P2856 are the inputs of the timer, outputs are P2857, P2858.

Dependency:

P2802[1] is active level for the timer.

MICROMASTER 440

Parameter List

6SE6400-5BB00-0BP0

251

Page 251
Image 251
Siemens 440 manual P2851 Mode timer, R2852 BO Timer, R2853 BO Nout timer, P2854 BI Timer, P2855 Delay time of timer