Parameter Description | Issue 01/06 |
r0064 | CO: Dev. frequency controller |
| Min: | - |
| Datatype: Float | Unit: Hz | Def: | - |
|
| Max: | - |
Displays actual deviation of speed controller.
Level
3
This value is calculated from the frequency setpoint (r0062) and the actual frequency (r0063).
Dependency:
Applies when vector control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0065 | CO: Slip frequency |
| Min: | - |
| Datatype: Float | Unit: % | Def: | - |
|
| Max: | - |
Level
3
Displays slip frequency of motor in [%] relative to the rated motor frequency (P0310).
Details:
For V/f control, see also P1335 (slip compensation).
r0066 | CO: Act. output frequency |
| Min: | - | Level |
| Datatype: Float | Unit: Hz | Def: | - | 3 |
|
| ||||
|
|
| Max: | - |
|
Displays actual output frequency.
Note:
The output frequency is limited by the values entered in P1080 (min. frequency) and P1082 (max. frequency).
r0067 | CO: Act. output current limit |
| Min: | - |
| Datatype: Float | Unit: A | Def: | - |
|
|
| Max: | - |
Displays valid maximum output current of inverter.
Level
3
Parameter r0067 is influenced/determined by the following factors:
-Rated motor current P0305
-Motor overload factor P0640
-Motor protection in dependency of P0610
-r0067 is less than or equal to maximum inverter current r0209
-Inverter protection in dependency of P0290
Motor
Inverter
P0305
P0640
Motor protection
Min
r0209
Inverter protection
r0067
Note:
A reduction of r0067 may indicate an inverter overload or a motor overload.
r0068 | CO: Output current |
| Min: | - |
| Datatype: Float | Unit: A | Def: | - |
|
| Max: | - |
Level
3
Displays unfiltered [rms] value of motor current [A].
Note:
This is used for the process control (contrary to the smoothed output current r0027, that is used for display).
r0069[6] | CO: Act. phase currents |
| Min: | - |
| Datatype: Float | Unit: A | Def: | - |
|
| Max: | - |
Displays phase currents.
Index:
r0069[0] : U_phase
r0069[1] : V_phase
r0069[2] : W_phase
r0069[3] : Offset U_phase
r0069[4] : Offset V_phase
r0069[5] : Offset W_phase
Level
4
38 | MICROMASTER 440 Parameter List |