Wiring Precautions

Wiring Precautions

Section 3-6

Attach the modified cable to the XW2D-40G6 Connector-Terminal Block Conversion Unit.

XW2D-40G6 Connector-

Terminal Block Conversion Unit

XW2Z-100J-C1 or

XW2Z-200J-C1

RS-422A Cable

RS-422A Connecting Cable

Connector-Terminal Block

 

 

Conversion Unit terminal

No.

Signal

number

 

 

2

SDB+

A18

 

 

 

1

SDA

A17

 

 

 

8

RDB+

B18

 

 

 

6

RDA

B17

 

 

 

3-6 Wiring Precautions

3-6-1 Reducing Electrical Noise

I/O Signal Wiring

Whenever possible, place I/O signal lines and power lines in separate ducts or raceways both inside and outside of the control panel.

1

2

Suspended ducts

 

1

2

 

 

 

 

 

 

 

 

 

In-floor ducts

1 = I/O cables

2 = Power cables

12

Conduits

If the I/O wiring and power wiring must be routed in the same duct, use shielded cable and connect the shield to the GR terminal to reduce noise.