Monitoring High-speed Counter Movement (Mode 1)

Pulse Inputs

Section 7-5

Monitoring High-speed Counter Movement (Mode 1)

Note

This function monitors the change in a high-speed counter’s PV (travel dis- tance) regularly at the preset sampling period. The sampling period can be set between 1 and 9,999 ms.

If the sampling time is set to 0, the change will be sampled once each cycle. The change in the high-speed counter PV (travel distance) is stored in A604 and A605 (high-speed counter 1) or A606 and A607 (high-speed counter 2). Status Flags A608.06 and A609.06 can be checked to determine whether or not change is being measured.

(1)The change (per sampling period) is refreshed during the Motion Control Module’s I/O refreshing.

(2)The change in the high-speed counter PV’s is output as an absolute val- ue.

Word

Bits

Function

Details

 

 

 

 

A604 and

00 to 15

High-speed Counter 1

Contains the change in high-speed

A605

 

Monitor Data

counter 1.

 

 

 

The change in the high-speed

 

 

 

counter PV during the specified sam-

 

 

 

pling period is stored in 8-digit hexa-

 

 

 

decimal (0000 0000 to FFFF FFFF).

 

 

 

 

A606 and

00 to 15

High-speed Counter 2

Contains the change in high-speed

A607

 

Monitor Data

counter 2.

 

 

 

The change in the high-speed

 

 

 

counter PV during the specified sam-

 

 

 

pling period is stored in 8-digit hexa-

 

 

 

decimal (0000 0000 to FFFF FFFF).

 

 

 

 

A608

06

High-speed Counter 1

Measuring Flag

 

 

Status Flag

OFF: The high-speed counter move-

 

 

 

 

 

 

ment measurement operation

 

 

 

is stopped.

 

 

 

ON: The high-speed counter move-

 

 

 

ment is being measured.

 

 

 

 

A609

06

High-speed Counter 2

Measuring Flag

 

 

Status Flag

OFF: The high-speed counter move-

 

 

 

 

 

 

ment measurement operation

 

 

 

is stopped.

 

 

 

ON: The high-speed counter move-

 

 

 

ment is being measured.

 

 

 

 

The pulse input’s counter data display must be set to counter movements (mode 1) in the System Setup in advance. The sampling period must also be set in the System Setup.

Tab page

 

Function

Details

 

 

 

 

 

Pulse input

Counter 1

 

Counter data

1 hex:

 

 

 

display

Counter movements (mode 1)

 

 

 

 

 

 

 

 

Sampling time

Set the sampling time when mea-

 

 

 

(mode 1)

suring counter movement.

 

 

 

 

0000: Cycle time

 

 

 

 

0001 to 270F hex: 1 to 9999 ms

 

 

 

 

(unit: 1 ms)

 

 

 

 

 

 

Counter 2

 

Counter data

1 hex:

 

 

 

display

Counter movements (mode 1)

 

 

 

 

 

 

 

 

Sampling time

Set the sampling time when mea-

 

 

 

(mode 1)

suring counter movement.

 

 

 

 

0000: Cycle time

 

 

 

 

0001 to 270F hex: 1 to 9999 ms

 

 

 

 

(unit: 1 ms)

 

 

 

 

 

157

Page 180