Omron FQM1-MMP21, FQM1-CM001, FQM1-MMA21 Serial Communications, Section, System Setup

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 158
Image 158
Smart Active Parts Communications Settings

Serial Communications

Section 6-1

NS-series PT

Smart Active Parts

NT Link

Coordinator Module

FQM1

Protocol

Servo parameters or

 

 

 

other data

 

conversion

 

RS-422A

W-series or

SMARTSTEP

Servo Driver

W-series or

SMARTSTEP Servo Driver

Note When the Serial Gateway function is used, the FQM1 receives FINS com- mands (encapsulated W-series or SMARTSTEP commands) via the RS-422A port from NT-series PTs or personal computers and converts them to W- series or SMARTSTEP Servo Driver commands (removes the encapsulation) and transfers them to the W-series or SMARTSTEP Servo Drivers.

System Setup

 

Item

Settings

Default

Enabled

 

 

 

 

Drive Tab Page

Mode

Serial Gateway or Non-procedural

Serial Gateway

Each cycle

 

 

(no-protocol)

 

 

 

 

 

 

 

 

RS-422 Response Time-

0.1 to 25.5 s (unit: 0.1 s)

5 s

 

 

out of Command

 

 

 

 

 

 

 

 

Note

Smart Active Parts Communications Settings

The settings are made using CX-Programmer Ver. 5.0@ menus.

When using NS-series Smart Active Parts for Servo Drivers with the FQM1, set the Destination Unit No. (U) to 251 on the Smart Active Parts Communica- tions Settings Screen. No. 251 indicates the RS-422A port for the FQM1.

135

Page 158
Image 158
Omron FQM1-MMP21, FQM1-CM001 Serial Communications, Section, System Setup, Smart Active Parts Communications Settings