2-6 Module Current Consumption

Maximum Current and

Maximum Total Power

Consumption

The amount of current/power that can be supplied to the Modules mounted in the FQM1 is limited. Refer to the following tables when designing your system so that the total current consumption of the mounted Modules does not exceed the maximum current for each voltage system and the total power consumption does not exceed the maximum for the Power Supply Unit.

The following table shows the maximum currents and power that can be sup- plied by Power Supply Units to the Controller.

Power Supply

Max. current consumption

Max. total

Unit

 

 

 

power con-

5-V system

24-V system

24-V system

 

sumption

 

(internal logic)

(analog)

(service)

 

 

 

 

 

 

 

CJ1W-PA202

2.8 A

0.4 A

None

14 W

 

 

 

 

 

CJ1W-PA205R

5.0 A

0.8 A

None

25 W

 

 

 

 

 

Current Consumption for Each Module

Current Consumption for 5-V System

Name

Model

5-V system current

 

 

consumption (A)

 

 

 

Coordinator Module

FQM1-CM001

0.47 (See note.)

Note The listed value includes the

 

 

current consumption for the

 

 

CX-Programmer.

 

 

 

 

 

End Module

FQM1-TER01

Included in Coordinator

 

 

Module current consumption

 

 

 

Note The current consumption increases by 0.15 A/Module if NT-AL001 Link Adapt- ers are used.