Omron FQM1-CM001, FQM1-MMA21, FQM1-MMP21 3-2Application Precautions, Safety Precautions

Models: FQM1-MMP21 FQM1-MMA21 FQM1-CM001

1 414
Download 414 pages 44.52 Kb
Page 15
Image 15
3-2 Application Precautions

Safety Precautions

3

Locations subject to static electricity or other forms of noise

Locations subject to strong electromagnetic fields

Locations subject to possible exposure to radioactivity

Locations close to power supplies

!Caution The operating environment of the FQM1 System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the FQM1 System. Make sure that the operating environment is within the speci- fied conditions at installation and remains within the specified conditions dur- ing the life of the system.

3-2 Application Precautions

!WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.

Always connect to a ground of 100 or less when installing the FQM1. Not doing so may result in electric shock.

Always connect to a ground of 100 or less when short-circuiting the functional ground and line ground terminals of the Power Supply Unit, in particular.

Always turn OFF the power supply to the FQM1 before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.

Mounting or dismounting Power Supply Unit, Coordinator Module, Mo- tion Control Module, and End Module

Assembling the Modules

Setting DIP switches

Connecting or wiring the cables

Connecting or disconnecting the connectors

!Caution Failure to abide by the following precautions could lead to faulty operation of the FQM1 or the system, or could damage the FQM1. Always heed these pre- cautions.

Always use the CX-Programmer (Programming Device for Windows) to create new cyclic tasks and interrupt tasks.

The user program and parameter area data in Coordinator Module and Motion Control Modules is backed up in the built-in flash memory. Do not turn OFF the power supply to the FQM1 while the user program or param- eter area data is being transferred. The data will not be backed up if the power is turned OFF.

The FQM1 will start operating in RUN mode when the power is turned ON with the default settings (i.e., if the operating mode at power ON (startup mode) setting in the System Setup is disabled).

Configure the external circuits so that the control power supply turns ON after the power supply to the FQM1 turns ON. If the power is turned ON in the opposite order, the built-in outputs and other outputs may momen- tarily malfunction and the control outputs may temporarily not operate cor- rectly.

xvi

Page 15
Image 15
Omron FQM1-CM001, FQM1-MMA21, FQM1-MMP21 operation manual 3-2Application Precautions, Safety Precautions