Pulse Inputs

Section 7-5

7-5-9 Pulse Input Function Procedures

High-speed Counter Procedure

1,2,3... 1. Determine the Input Mode, reset method, and Numeric Range.

Counting Speed: 50 kHz or 500 kHz

Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc- tion

Reset method: Phase Z and software reset, or Software reset

Counter Operation: Circular Counter or Linear Counter

2.Wire the input.

3.Make the necessary System Setup settings.

Counting Speed: 50 kHz or 500 kHz

Input Mode: Phase Differential, Increment/Decrement, or Pulse + Direc- tion

Reset: Phase Z and software reset, or Software reset

Counter Operation: Circular Counter or Linear Counter

Count Check Method: Target-value Comparison or Range Comparison

4.If the count check is being used, determine the count check (comparison) method.

5.Create the necessary ladder programming.

Turn ON the High-speed Counter 1 or 2 Start Bit (A610.00 or A611.00) and start the high-speed counter.

CTBL(882) instruction: Specifies the port, registers the comparison table, and starts comparison.

INI(880) instruction: Specifies the port, changes the PV, and starts com- parison.

PRV(881) instruction: Specifies the port and reads the high-speed counter PV.

160

Page 183
Image 183
Omron FQM1-CM001, FQM1-MMA21, FQM1-MMP21 operation manual Pulse Input Function Procedures, High-speed Counter Procedure