Installation

Section 3-1

3-1-2 Installation in a Control Panel

The FQM1 must be mounted inside a control panel on DIN Track.

AC100 -240V INPUT

L1

L2/N

NC

NC

Note The FQM1 must be mounted on DIN Track. It cannot be mounted with screws.

Wiring Ducts

Use wiring ducts to wire the FQM1’s built-in I/O. Install the wiring ducts to facilitate wiring the built-in I/O. It is handy to have the duct at the same height as the FQM1.

Duct

Unit

Duct

20 mm min.

DIN Track

20 mm min.

Wiring Duct Example

The following example shows the proper installation of wiring ducts.

30 mm

30 mm

40 mm

Duct

PLC

Mounting bracket

FQM1

80.0 mm

Note Tighten terminal block screws and cable screws to the following torques.

Terminal Screws

M4: 1.2 N·m

M3: 0.5 N·m

53

Page 76
Image 76
Omron FQM1-MMA21 Installation in a Control Panel, FQM1 must be mounted inside a control panel on DIN Track, Wiring Ducts